| 2001-08-15 00:00:00 | *******************PROVISO************** | | | | | | | | | PRIOR TO CONNECTING TO EXISTING | | | DUCTWORK, CALL FOR AN INSPECTION. | | | | | | PLEASE INDICATE LOCATION OF OVERFLOW TO | | | DRAIN PAN,AS PER 1997 SMC 304.8.6.1 - | | | A SEPARATE DRAIN LINE IS REQUIRED AND | | | SHALL TERMINATE AT A CONSPICUOUS POINT | | | TO SERVE AS AN ALARM THAT THE REGULAR | | | DRAIN LINE IS RESTRICTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|