| Plan Review Notes For Permit 01071397 |
| Permit Number |
01071397 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT THE AIC RATINGS | | | FOR MLO PANEL"H" HAS BEEN CHANGED TO | | | 14,000. PLEASE NOTE THAT PER AIC | | | CALCULATIONS ON PLANS, 14,000 IS NOT | | | ENOUGH. PLEASE NOTE THAT BRKRS IN PANEL | | | NEED TO BE CHANGED OUT BACK TO THE | | | 22,000 AS ORIG CALCULATED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|