Plan Review Notes
Plan Review Notes For Permit 01071397
Permit Number 01071397
Review Stop E
Sequence Number 5
Notes
Date Text
2002-01-08 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE THAT THE AIC RATINGS
 FOR MLO PANEL"H" HAS BEEN CHANGED TO
 14,000. PLEASE NOTE THAT PER AIC
 CALCULATIONS ON PLANS, 14,000 IS NOT
 ENOUGH. PLEASE NOTE THAT BRKRS IN PANEL
 NEED TO BE CHANGED OUT BACK TO THE
 22,000 AS ORIG CALCULATED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372