| Plan Review Notes For Permit 01071397 |
| Permit Number |
01071397 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-09-06 00:00:00 | PLUMBING PLAN REVIEW, DENIED. | | | PREVIOUS COMMENTS NOT ADDRESSED | | | (1)SHT A-12 ELVATION DETAIL REQUIRED FOR | | | BREAK RM SINK,FACBC-94 SEC 4.24 HGTH 34" | | | FF, KNEE CLEARANCE, CLEAR FLR SPACE. | | | (2) SHT A-2 CONFLICTS WITH SHT P-2, | | | PLBG FIXTURE LEGEND CALLS FOR A HILO D/F | | | SHTA-2 ONLY HAS SPACE FOR A SINGLE D/F? | | | (3) SHT P-1 WATER HEATER INSTALLED ABOVE | | | CEILING, SEC 501.7 W/H TO BE READLY ACCE | | | SSIBLE, SHOW A DETAIL OF A WORKING PLAT | | | FORM WITH A SHIPS LADDER FIXED IN PLACE. | | | (4A) SHT P-2 PLBG NOTE #14 REFERENCE TO | | | AIR CHAMBERS,SEC 607.8.3 TO BE ACCESSBLE | | | AND RECHARGEABLE, OR DELETE NOTE. | | | (B) WATER RISER DETAIL, SHOCK ARESSTORS | | | ARE NOT SHOWN AS REQUIRED BY MFG FOR | | | LOCATION AND PLACEMENT. | | | (5) SHT A-12 MEM & WOMENS H/C REST ROOM | | | STALL,SHALL COMPLY W/FACBC SEC 4.17.3& | | | FIG 30E,FOR SIZE AND ARRANGMENT OF PLBG | | | FIXTURES,INC INCLUDE ALL DIMENSIONS. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|