Plan Review Notes
Plan Review Notes For Permit 01071397
Permit Number 01071397
Review Stop P
Sequence Number 3
Notes
Date Text
2001-09-06 00:00:00PLUMBING PLAN REVIEW, DENIED.
 PREVIOUS COMMENTS NOT ADDRESSED
 (1)SHT A-12 ELVATION DETAIL REQUIRED FOR
 BREAK RM SINK,FACBC-94 SEC 4.24 HGTH 34"
 FF, KNEE CLEARANCE, CLEAR FLR SPACE.
 (2) SHT A-2 CONFLICTS WITH SHT P-2,
 PLBG FIXTURE LEGEND CALLS FOR A HILO D/F
 SHTA-2 ONLY HAS SPACE FOR A SINGLE D/F?
 (3) SHT P-1 WATER HEATER INSTALLED ABOVE
 CEILING, SEC 501.7 W/H TO BE READLY ACCE
 SSIBLE, SHOW A DETAIL OF A WORKING PLAT
 FORM WITH A SHIPS LADDER FIXED IN PLACE.
 (4A) SHT P-2 PLBG NOTE #14 REFERENCE TO
 AIR CHAMBERS,SEC 607.8.3 TO BE ACCESSBLE
 AND RECHARGEABLE, OR DELETE NOTE.
 (B) WATER RISER DETAIL, SHOCK ARESSTORS
 ARE NOT SHOWN AS REQUIRED BY MFG FOR
 LOCATION AND PLACEMENT.
 (5) SHT A-12 MEM & WOMENS H/C REST ROOM
 STALL,SHALL COMPLY W/FACBC SEC 4.17.3&
 FIG 30E,FOR SIZE AND ARRANGMENT OF PLBG
 FIXTURES,INC INCLUDE ALL DIMENSIONS.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233