2001-09-10 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT CLEARENCES FOR
 TRANSFORMER AND DISCONNECT DOES NOT
 SEEM TO MEET 110-26. PLEASE CALRIFY
  
 2)NOTE: PLEASE NOTE THAT LOAD CALCULAT-
 -IONS FOR TRACK LIGHTING NOT SHOWN PER
 220-12B. PLANS SHOW 48' OF TRACK? AT
 150W PER 2', SHOULD SHOW AT 7200W.
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  