| Plan Review Notes For Permit 01071397 |
| Permit Number |
01071397 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT CLEARENCES FOR | | | TRANSFORMER AND DISCONNECT DOES NOT | | | SEEM TO MEET 110-26. PLEASE CALRIFY | | | | | | 2)NOTE: PLEASE NOTE THAT LOAD CALCULAT- | | | -IONS FOR TRACK LIGHTING NOT SHOWN PER | | | 220-12B. PLANS SHOW 48' OF TRACK? AT | | | 150W PER 2', SHOULD SHOW AT 7200W. | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|