2001-08-15 00:00:00********************DENIED**************
  
  
 PLEASE INDICATE ON PLAN WHERE THE
 OVERFLOW FOR THE FCU AUXILIARY DRAIN
 PAN TERMINATES.THIS LINE SHALL
 TERMINATE AT A CONSPICUOUS POINT TO
 SERVE AS AN ALARM THAT THE REGULAR
 DRAIN IS RESTRICTED.
  
  