2001-07-31 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS WITH NEXT SUBMITTAL.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. PLEASE PROVIDE LOCATIONS OF ALL
 FIRE ALARM DEVICES WITHIN TENANT
 SPACE.
 3) PLEASE PROVIDE AN OCCUPANT LOAD
 COUNT AND LIFE SAFETY PLAN TO THIS
 OFFICE.
 4) WRONG EDITION OF THE STANDARD
 BUILDING CODE REFERENCED. SHOULD READ
 1997 EDITION.
 5) PLEASE INDICATE EXIT DISCHARGE
 LOCATIONS FOR ALL EXIT DOORS.
  