| 2001-08-14 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT TRANSFORMER IS |
| | BEING SHOWN INSTALLED IN A STORAGE |
| | ROOM?PLEASE NOTE 110-26 FOR THIS SPACE |
| | TO BE DEDICATED ELEC. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THE DISCONNECT |
| | SHOWN ON RISER DIAGRAM IS NOT SHOWN ON |
| | PLANS. PLEASE NOTE 240-21 FOR 10' TAP |
| | RULE FOR REQ`D DISCONNECT FOR SECONDARY |
| | OF TRANSFORMER ALSO OCP REQ`D PER 384-16 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PLEASE SUBMIT FOR DISCONNECT FROM |
| | TRANSFORMER TO PANEL"A". |
| | |
| | 4)NOTE: PLEASE CLARIFY BOX SHOWN AS "J" |
| | ON TRANSFORMER? JUNCTION BOX? |
| | |
| | 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) PER 215-3/230-42 |
| | |
| | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | FOR TRACK LIGHTING PER 220-12B. |
| | |
| | 7)NOTE: PLEASE CLARIFY GROUNDING |
| | ATTACH--MENT FOR TRANSFORMER PER 250-30. |
| | |
| | PLEASE SUBMIT ALL OF THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |