| Plan Review Notes For Permit 01071397 |
| Permit Number |
01071397 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-14 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW 01071397 | | | 701 S ROSEMARY# 103 | | | SCHIAPPA CONST CORP | | | TEL: 954/ 658- 7493 | | | | | | 1)- SHEET A-4 ELEVATION #2 FIXED GLASS | | | IS THIS EXISTING OR IS THIS PART OF THE | | | BUILD OUT? THE SAME ISSUE WITH THE FRONT | | | DOORS? IF PART OF THE TENANT BUILD OUT | | | PRODUCT TESTING FOR GLAZED OPENINGS WILL | | | BE REQUIRED, 2 COPIES OF PRODUCT TESTING | | | FOR LARGE MISSLE IMPACT RESISTANCE TEST- | | | ING, SBCCI OR DADE COUNTY ACCEPTED. | | | | | | 2)- SHEET A-2 / A-8 BACK EXIT STAIRS, | | | VERTICAL ACCESSIBILITY, FL ACC CODE | | | 4.1.3.(9) AN ACCESIBILE MEANS OF EGRESS | | | SHALL BE PROVIDED IN THE SAME NUMBER AS | | | REQUIRED FOR EXITS BY LOCAL BUILDING / | | | LIFE SAFETY REGULATIONS. | | | | | | 3)- SBC 903.1 AN APPROVED FIRE SPRINKLER | | | AND DEVISES SHALL BE USSED IN AUTOMATIC | | | SPRINKLKER SYSTEMS AND THE COMPLETE LAY- | | | OUT OF THE SYSTEM. | | | | | | 4)- SBC 905.1FIRE ALARM SYSTEM NO PLANS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|