2001-12-05 00:00:00*******************PROVISO**************
  
  
 EXHAUST DUCT FOR DRYER SHALL NOT EXCEED
 25'.THERE SHALL BE A DEDUCTIONS OF 2
 1/2' FOR EACH 45 DEGREE BEND AND 5' FOR
 EACH 90 DEGREE BEND.THE WALL OR ROOF
 CAP SHALL BE NONSCREENED WITH ADRAFT
 DRAFT DAMPER.
  
 PLEASE INDICATE HOW COMBUSTIBLE LINT
 WILL BE REMOVED (CLEANOUTS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.