Plan Review Notes
Plan Review Notes For Permit 01071374
Permit Number 01071374
Review Stop R
Sequence Number 2
Notes
Date Text
2001-10-26 00:00:00SHEET C1, FRAMING NOTES.THE ARCHITECTS
 DISCLAIMER FOR STRUCTURAL
 RESPONSIBILITY IS NOT ACCEPTABLE.IN
 DELEGATING ENGINEERING RESPONSIBILITY
 TO A SPECIALTY ENGINEER IT IS THE
 DESIGNER OF RECORD'S DUTYTO NOTE THE
 LOCATION, NATURE, MAGNITUDE AND
 DIRECTION OF LOADS TO BE RESISTED.AT
 TIME OF PERMIT APPLICATION PROVIDE
 SIGNED AND SEALED CALCULATIONS
 DEMONSTRATING COMPLIANCE WITH SBC 1601.
  
 IN THE ABSENCE OF A SURVEY AND SITE
 PLANA COMPLETE REVIEW FOR CODE
 COMPLIANCE IS NOT POSSIBLE.
  
 SHEET A10 OF THE TYPE 3 BUILDING. TERMS
 LIKE "(STRINGER BEARING TO COMPLY W/ SBC
 1997)" ARE NOT ACCEPTABLE SUBSTITUTES
 FOR SPECIFIC DESIGN INFORMATION.SEE
 SBC104.2.SAME SHEET, THE REFERENCE
 SFBC 2907.3 (C) IS WITHOUTSTANDING.
  
 WITH REGARDS TO FREE AREA OF A SOFFIT
 SCREEN VENT, A 7" X 22" SCREEN CAN
 PROVIDE 40% TO 60% OF FREE AREA AND NOT
 THE SIZE OF THE ROUGH OPENING.
 FURTHER, WHEN INSTALLED SUBSEQUENT TO
 WIRE LATH ADDITIONAL AREA REDUCTION
 MUST BE ALLOWED FOR.
  
 SEE THE 8/27/01 LIST FOR IMPACT FEES,
 RESIDENT INSPECTOR, ETC.