| 2001-10-26 00:00:00 | SHEET C1, FRAMING NOTES.THE ARCHITECTS |
| | DISCLAIMER FOR STRUCTURAL |
| | RESPONSIBILITY IS NOT ACCEPTABLE.IN |
| | DELEGATING ENGINEERING RESPONSIBILITY |
| | TO A SPECIALTY ENGINEER IT IS THE |
| | DESIGNER OF RECORD'S DUTYTO NOTE THE |
| | LOCATION, NATURE, MAGNITUDE AND |
| | DIRECTION OF LOADS TO BE RESISTED.AT |
| | TIME OF PERMIT APPLICATION PROVIDE |
| | SIGNED AND SEALED CALCULATIONS |
| | DEMONSTRATING COMPLIANCE WITH SBC 1601. |
| | |
| | IN THE ABSENCE OF A SURVEY AND SITE |
| | PLANA COMPLETE REVIEW FOR CODE |
| | COMPLIANCE IS NOT POSSIBLE. |
| | |
| | SHEET A10 OF THE TYPE 3 BUILDING. TERMS |
| | LIKE "(STRINGER BEARING TO COMPLY W/ SBC |
| | 1997)" ARE NOT ACCEPTABLE SUBSTITUTES |
| | FOR SPECIFIC DESIGN INFORMATION.SEE |
| | SBC104.2.SAME SHEET, THE REFERENCE |
| | SFBC 2907.3 (C) IS WITHOUTSTANDING. |
| | |
| | WITH REGARDS TO FREE AREA OF A SOFFIT |
| | SCREEN VENT, A 7" X 22" SCREEN CAN |
| | PROVIDE 40% TO 60% OF FREE AREA AND NOT |
| | THE SIZE OF THE ROUGH OPENING. |
| | FURTHER, WHEN INSTALLED SUBSEQUENT TO |
| | WIRE LATH ADDITIONAL AREA REDUCTION |
| | MUST BE ALLOWED FOR. |
| | |
| | SEE THE 8/27/01 LIST FOR IMPACT FEES, |
| | RESIDENT INSPECTOR, ETC. |