2001-08-27 00:00:00SHEET C1 SHOULD CITE THE 1997 SBC AS
 THEGOVERNING DESIGN CODE AND NOT " ...
 AS APPLICABLE ..."
  
 THERE WAS NO SITE PLAN OR SURVEY
 INCLUDED WITH THE PLANS SO A COMPLETE
 REVIEW FOR CODE COMPLIANCE WAS NOT
 POSSIBLE.
  
 SOIL TREATMENT REQUIREMENTS SHOULD BE
 ADDED TO THE FOUNDATION NOTES.SEE SBC
 2304.1.2 AS AMENDED.
  
 PLANS SUBMITTED FOR PUBLIC RECORD ARE
 REQUIRED TO BE SIGNED, SEALED AND DATED
 BY THE DESIGNER OF RECORD.SEE FS 471
 AND 481.
  
 SHEET C1 FRAMING NOTES, NOTE 6."THE
 ARCHITECT ACCEPTS NO RESPONSIBILITY FOR
 STRUCTURAL ..." A REGISTERED DESIGN
 PROFESSIONAL MUST ASSUME RESPONSIBILITY
 FOR THE STRUCTURAL REQUIREMENTS.
  
 SHEET C1 THE LOAD SCHEDULE IS NOT CLEAR
 AS TO WHETHER ASCE 7 OR 1606.2 WAS USED
 FOR THE WIND DESIGN.
  
 PROVIDE ENERGY CODE CALCULATIONS WITH
 THE PERMIT APPLICATION.
  
 PROVIDE A TEST REPORT OR NOTICE OF
 ACCEPTANCE FOR THE ROOF COVERING WITH
 THE PERMIT APPLICATION.
  
 SHEET A2, PROVIDE THE SUPPORTING
 DOCUMENTATION FOR THE "SAFE LOAD TABLE"
  
 SHEET A2. NOTE THE REQUIREMENT FOR
 SAFETY GLASS IN ACCORDANCE WITH SBC
 2405.2 #3 FOR THE GLAZING IN THE
 VICINITY OF THE ENTRANCE DOORS.A
 GENERIC NOTE ON THE COVER SHEET IS
 INSUFFICIENT.
  
 SHOW A CONSTRUCTION DETAIL FOR THE AREA
 SHOWN AS "FRAMED DOWNED" ON SHEET A4.
  
 SHEET A9.SHOW THE STAIR STRINGER AND
 TREAD SIZE AND MATERIAL SPECIFICATION.
  
 SHEET A9, STAIR DETAIL, HAS CONFLICTING
 INFORMATION FOR THE PICKET SPACING (4 -
 6) AND FASTENER SIZE (#12 SCREW AND 5/8"
 SCREW)PLEASE REVISE AS NECESSARY.
  
 PLEASE EXPLAIN HOW THE DETAIL SHOWN AS
 "OPTION 1" ON SHEET A9 WILL ADEQUATELY
 ADDRESS GRAVITY LOADS.
  
 THE DETAIL ON SHEET A10 CALLS FOR FRT
 SHEATHING FROM A CENTERLINE WHILE SBC
 704.4.1 #2 REQUIRES FRT TO 4' FROM
 EITHER SIDE OF THE WALL.REVISE AS
 NECESSARY.
  
 PLEASE SPECIFY THE FREE AREA OF THE 6" X
 24" SOFFIT VENTS TO BE USED SO THAT
 COMPLIANCE WITH SBC 2309.7 MAY BE
 DETERMINED.
  
 SHOW A DETAIL FOR THE WINDOW AND DOOR
 BUCK CONNECTIONS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY AND THE PERMIT PLANS STAMPED BY
 THEM.CALL 233-5025 FOR MORE
 INFORMATION.
  
 A SEPARATE PERMIT APPLICATION IS
 REQUIRED FOR EACH TOWNHOUSE UNIT.
  
 ON BUILDING TYPE 3, UNITS LABELED E MUST
 COMPLY WITH SBC 1010.4.
  
 A RESIDENT INSPECTOR MAY BE REQUIRED FOR
 THIS PROJECT.CONTACT DON NEELY AT
 659-8093 X 8333 FOR MORE INFORMATION.