| 2001-08-27 00:00:00 | SHEET C1 SHOULD CITE THE 1997 SBC AS |
| | THEGOVERNING DESIGN CODE AND NOT " ... |
| | AS APPLICABLE ..." |
| | |
| | THERE WAS NO SITE PLAN OR SURVEY |
| | INCLUDED WITH THE PLANS SO A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE WAS NOT |
| | POSSIBLE. |
| | |
| | SOIL TREATMENT REQUIREMENTS SHOULD BE |
| | ADDED TO THE FOUNDATION NOTES.SEE SBC |
| | 2304.1.2 AS AMENDED. |
| | |
| | PLANS SUBMITTED FOR PUBLIC RECORD ARE |
| | REQUIRED TO BE SIGNED, SEALED AND DATED |
| | BY THE DESIGNER OF RECORD.SEE FS 471 |
| | AND 481. |
| | |
| | SHEET C1 FRAMING NOTES, NOTE 6."THE |
| | ARCHITECT ACCEPTS NO RESPONSIBILITY FOR |
| | STRUCTURAL ..." A REGISTERED DESIGN |
| | PROFESSIONAL MUST ASSUME RESPONSIBILITY |
| | FOR THE STRUCTURAL REQUIREMENTS. |
| | |
| | SHEET C1 THE LOAD SCHEDULE IS NOT CLEAR |
| | AS TO WHETHER ASCE 7 OR 1606.2 WAS USED |
| | FOR THE WIND DESIGN. |
| | |
| | PROVIDE ENERGY CODE CALCULATIONS WITH |
| | THE PERMIT APPLICATION. |
| | |
| | PROVIDE A TEST REPORT OR NOTICE OF |
| | ACCEPTANCE FOR THE ROOF COVERING WITH |
| | THE PERMIT APPLICATION. |
| | |
| | SHEET A2, PROVIDE THE SUPPORTING |
| | DOCUMENTATION FOR THE "SAFE LOAD TABLE" |
| | |
| | SHEET A2. NOTE THE REQUIREMENT FOR |
| | SAFETY GLASS IN ACCORDANCE WITH SBC |
| | 2405.2 #3 FOR THE GLAZING IN THE |
| | VICINITY OF THE ENTRANCE DOORS.A |
| | GENERIC NOTE ON THE COVER SHEET IS |
| | INSUFFICIENT. |
| | |
| | SHOW A CONSTRUCTION DETAIL FOR THE AREA |
| | SHOWN AS "FRAMED DOWNED" ON SHEET A4. |
| | |
| | SHEET A9.SHOW THE STAIR STRINGER AND |
| | TREAD SIZE AND MATERIAL SPECIFICATION. |
| | |
| | SHEET A9, STAIR DETAIL, HAS CONFLICTING |
| | INFORMATION FOR THE PICKET SPACING (4 - |
| | 6) AND FASTENER SIZE (#12 SCREW AND 5/8" |
| | SCREW)PLEASE REVISE AS NECESSARY. |
| | |
| | PLEASE EXPLAIN HOW THE DETAIL SHOWN AS |
| | "OPTION 1" ON SHEET A9 WILL ADEQUATELY |
| | ADDRESS GRAVITY LOADS. |
| | |
| | THE DETAIL ON SHEET A10 CALLS FOR FRT |
| | SHEATHING FROM A CENTERLINE WHILE SBC |
| | 704.4.1 #2 REQUIRES FRT TO 4' FROM |
| | EITHER SIDE OF THE WALL.REVISE AS |
| | NECESSARY. |
| | |
| | PLEASE SPECIFY THE FREE AREA OF THE 6" X |
| | 24" SOFFIT VENTS TO BE USED SO THAT |
| | COMPLIANCE WITH SBC 2309.7 MAY BE |
| | DETERMINED. |
| | |
| | SHOW A DETAIL FOR THE WINDOW AND DOOR |
| | BUCK CONNECTIONS. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO THE |
| | COUNTY AND THE PERMIT PLANS STAMPED BY |
| | THEM.CALL 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A SEPARATE PERMIT APPLICATION IS |
| | REQUIRED FOR EACH TOWNHOUSE UNIT. |
| | |
| | ON BUILDING TYPE 3, UNITS LABELED E MUST |
| | COMPLY WITH SBC 1010.4. |
| | |
| | A RESIDENT INSPECTOR MAY BE REQUIRED FOR |
| | THIS PROJECT.CONTACT DON NEELY AT |
| | 659-8093 X 8333 FOR MORE INFORMATION. |