Plan Review Notes
Plan Review Notes For Permit 01071374
Permit Number 01071374
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-16 00:00:00DENIED;
 1."B" UNIT RISER DIAGRAM. 2" WET VENT
 CAN HAVE A MAXIMUM OF 4 FIXTURE UNITS.
 VENT FOR WATER CLOSET WITH LAV, TUB,
 AND SHOWER MUST BE 3" AFTER SHOWER TO
 PROPERLY VENT W/C SPC SEC. 911.1.
 2.APPROVED UTILITYS PLANS ARE REQUIRED
 FOR FINAL PLUMBING PLAN REVIEW OF BUILD-
 INGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369