| Plan Review Notes For Permit 01071374 |
| Permit Number |
01071374 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-16 00:00:00 | DENIED; | | | 1."B" UNIT RISER DIAGRAM. 2" WET VENT | | | CAN HAVE A MAXIMUM OF 4 FIXTURE UNITS. | | | VENT FOR WATER CLOSET WITH LAV, TUB, | | | AND SHOWER MUST BE 3" AFTER SHOWER TO | | | PROPERLY VENT W/C SPC SEC. 911.1. | | | 2.APPROVED UTILITYS PLANS ARE REQUIRED | | | FOR FINAL PLUMBING PLAN REVIEW OF BUILD- | | | INGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|