| Plan Review Notes For Permit 01071358 |
| Permit Number |
01071358 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-17 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) DRINKING FOUNTAIN TO COMPLY WITH | | | FACBC-97 SEC 4.15 - 4.15.2 SPOUT HEIGHT, | | | 4.15.5 CLEAR FLOOR SPACE. PLEASE SHOW | | | THESE DETAILS ON PLANS. CLEAR FLOOR | | | SPACE NOT AVAILIBLE BECAUSE OF COUNTER. | | | | | | 2) BREAK ROOM SINK SHALL COMPLY WITH | | | FACBC-97 SEC 2.24 - 2.24.2 HEIGHT. | | | PLEASE SHOW DETAIL ON PLANS. | | | | | | 3) BECAUSE OF NEW FIXTURES AND BATHROOM | | | FIXTURES MOVING APPROX. 10' AND OTHER | | | FIXTURES BEING DEMO'ED PLEASE SUBMIT A | | | SANITARY RISER DIAGRAM. INDICATE PIPE | | | SIZE, HOW PIPES ARE TIEING INTO EXISTING | | | SANITARY, AND SHOW VENTING. | | | | | | 4) IF HOT WATER IS UTILIZED SHOW SOURCE | | | OF HOT WATER ON WATER RISER DIAGRAM. | | | | | | 5) SIGNAGE SHALL BE POSTED FOR HDCP | | | RESTROOM BY DOOR TO MAN TRAP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|