Plan Review Notes
Plan Review Notes For Permit 01071358
Permit Number 01071358
Review Stop P
Sequence Number 3
Notes
Date Text
2001-10-17 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) DRINKING FOUNTAIN TO COMPLY WITH
 FACBC-97 SEC 4.15 - 4.15.2 SPOUT HEIGHT,
 4.15.5 CLEAR FLOOR SPACE. PLEASE SHOW
 THESE DETAILS ON PLANS. CLEAR FLOOR
 SPACE NOT AVAILIBLE BECAUSE OF COUNTER.
  
 2) BREAK ROOM SINK SHALL COMPLY WITH
 FACBC-97 SEC 2.24 - 2.24.2 HEIGHT.
 PLEASE SHOW DETAIL ON PLANS.
  
 3) BECAUSE OF NEW FIXTURES AND BATHROOM
 FIXTURES MOVING APPROX. 10' AND OTHER
 FIXTURES BEING DEMO'ED PLEASE SUBMIT A
 SANITARY RISER DIAGRAM. INDICATE PIPE
 SIZE, HOW PIPES ARE TIEING INTO EXISTING
 SANITARY, AND SHOW VENTING.
  
 4) IF HOT WATER IS UTILIZED SHOW SOURCE
 OF HOT WATER ON WATER RISER DIAGRAM.
  
 5) SIGNAGE SHALL BE POSTED FOR HDCP
 RESTROOM BY DOOR TO MAN TRAP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377