| Plan Review Notes For Permit 01071358 |
| Permit Number |
01071358 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | ******************** UNSAT ************ | | | | | | 1)NOTE: PLANS NEED TO HAVE ALL BRANCH | | | CIRCUIT #`S SHOWN AND CORRELATE WITH | | | PANEL SCHEDULE TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE THAT PER FS/FAC | | | PLANS THAT ARE SIGNED AND SEALED BY AN | | | ARCH/ENGINEER MUST HAVE A TITLE BLOCK. | | | 61G15-23.002 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|