| Plan Review Notes For Permit 01071352 |
| Permit Number |
01071352 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-28 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PANEL IS SHOWN | | | HAVING A MCB W/ A MAIN DISCONNECT ON THE | | | OUTSIDE. PLEASE NOTE THAT PANEL MAY BE | | | MLO. | | | | | | 2) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | MAY BE #6 | | | | | | 3)NOTE: PLEASE NOTE THAT PLAN SHOWS 2/0 | | | CONDUCTORS. MAY BE 1/0. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | PLEASE NOTE THAT NOTES 1 AND 3 ARE JUST | | | NOTES AND THOSE ITEMS MAY STAY AS THEY | | | ARE IF DESIRED. PLEASE SUBMIT THE OTHERS | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | OR I CAN BE OF ANY ASSISTANCE, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|