Plan Review Notes
Plan Review Notes For Permit 01071352
Permit Number 01071352
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-28 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 HAVING A MCB W/ A MAIN DISCONNECT ON THE
 OUTSIDE. PLEASE NOTE THAT PANEL MAY BE
 MLO.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
 MAY BE #6
  
 3)NOTE: PLEASE NOTE THAT PLAN SHOWS 2/0
 CONDUCTORS. MAY BE 1/0.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 PLEASE NOTE THAT NOTES 1 AND 3 ARE JUST
 NOTES AND THOSE ITEMS MAY STAY AS THEY
 ARE IF DESIRED. PLEASE SUBMIT THE OTHERS
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 OR I CAN BE OF ANY ASSISTANCE, PLEASE
 CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372