| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-05 00:00:00 | *******************DENIED*************** | | | | | | CLARIFY SMOKE SYSTEM SEQUENCE OF | | | OPERATION FOR THE ATRIUM.PLAN | | | INDICATES AHU 1, 9 & 15 WILL SHUT DOWN. | | | PLAN SHEET M.01 SHOWS AHU 3 ALSO | | | SUPPLIES AIR AND TRANSFERS AIR TO THE | | | ATRIUM.WHY IS THIS UNIT NOT INCLUDED | | | IN THE SHUTDOWN? | | | | | | INDICATE ON PLAN RATING OF "SHAFT" | | | ENCLOSING DUCTS AND REFRIGERANT LINES. | | | CLARIFY SEPARATION ON THE SOUTH SHAFT, | | | PLAN SHEET M.02 & M.03 DO NOT INDICATE | | | ANY SEPARATION BETWEEN THE REFRIGRANT | | | LINES AND DUCTWORK.AS PER NFPA 90A | | | 3-3.4.3, SHAFTS THAT CONSITITUE AIR | | | DUCTS OR THAT ENCLOSE AIR DUCTS USED | | | FOR THE MOVEMENT OF ENVIRONMENTAL AIR | | | SHALL NOT ENCLOSE:(F) PIPING. | | | | | | INDICATE CALCULATION FOR ATRUIM ON PLAN | | | SHOWING COMPLIANCE WITH 414.4.2. | | | | | | SEE FIRE DEPT COMMENTS ON KITCHEN HOOD. | | | | | | PLEASE PROVIDE TEST CRITERIA FOR SMOKE | | | EVACUATION PRIOR TO FINAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388 |
|