Plan Review Notes
Plan Review Notes For Permit 01071349
Permit Number 01071349
Review Stop M
Sequence Number 3
Notes
Date Text
2002-01-05 00:00:00*******************DENIED***************
  
 CLARIFY SMOKE SYSTEM SEQUENCE OF
 OPERATION FOR THE ATRIUM.PLAN
 INDICATES AHU 1, 9 & 15 WILL SHUT DOWN.
 PLAN SHEET M.01 SHOWS AHU 3 ALSO
 SUPPLIES AIR AND TRANSFERS AIR TO THE
 ATRIUM.WHY IS THIS UNIT NOT INCLUDED
 IN THE SHUTDOWN?
  
 INDICATE ON PLAN RATING OF "SHAFT"
 ENCLOSING DUCTS AND REFRIGERANT LINES.
 CLARIFY SEPARATION ON THE SOUTH SHAFT,
 PLAN SHEET M.02 & M.03 DO NOT INDICATE
 ANY SEPARATION BETWEEN THE REFRIGRANT
 LINES AND DUCTWORK.AS PER NFPA 90A
 3-3.4.3, SHAFTS THAT CONSITITUE AIR
 DUCTS OR THAT ENCLOSE AIR DUCTS USED
 FOR THE MOVEMENT OF ENVIRONMENTAL AIR
 SHALL NOT ENCLOSE:(F) PIPING.
  
 INDICATE CALCULATION FOR ATRUIM ON PLAN
 SHOWING COMPLIANCE WITH 414.4.2.
  
 SEE FIRE DEPT COMMENTS ON KITCHEN HOOD.
  
 PLEASE PROVIDE TEST CRITERIA FOR SMOKE
 EVACUATION PRIOR TO FINAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved