| 2001-12-31 00:00:00 | 1) ATRIUM NOTES SECTION A1.1 INDICATES |
| | THAT THE ATRIUM SMOKE EXHAUST WILL |
| | BE TESTED BY A THIRD PARTY PRIOR TO |
| | ISSUANCE OF FINAL CERTIFICATE. PLEASE |
| | BE ADVISED THAT THE ATRIUM SYSTEM WILL |
| | BE TESTED WITH CITY OFFICIALS AFTER |
| | BEING NOTIFIED BY THE CONTRACTOR. PLEASE |
| | PROVIDE TESTING REQUIREMENTS FOR THE |
| | ATRIUM SYSTEM ON THE PLANS. |
| | 2) ALSO NO DETAILS PROVIDED ON THE |
| | LOCATION, TYPE, OR IDENTITY OF THE |
| | FIREFIGHTER SMOKE EXHAUST PANEL |
| | REQUIRED PER NFPA 101, THE LIFE SAFETY |
| | CODE, SECTION 6-2.2.3.5, SECTION (G) |
| | 3) THE NOTES REGARDING THE STOVE AND |
| | ASSOCIATED EQUIPMENT WILL PROBABLY NOT |
| | BE ALLOWED. ALL OF THE REQUIREMENTS OF |
| | NFPA 96 MUST BE MET SINCE THE |
| | RESIDENTIAL STOVE WILL BE LOCATED IN |
| | A COMMERCIAL BUILDING. |
| | 4) HOW DOES THE ATRIUM SMOKE EXHAUST |
| | WORK SHOULD LOSS OF POWER OCCURS. |
| | 5) THE FIRE DEPARTMENT CONNECTION FOR |
| | THE SPRINKLER SYSTEM MUST FACE TOWARDS |
| | THE FIRE HYDRANT AND NOT AWAY FROM IT. |
| | 6) PLEASE INDCIATE NUMBER OF AIR |
| | CHANGES FOR ATRIUM SMOKE EXHAUST SYSTEM |
| | AND ANY ALL DEVICES THAT WILL ACTIVATE |
| | IT. |
| | 7) SINCE DOORS OPEN FOR MAKE-UP AIR |
| | ARE THERE ANY PROBLEMS WITH SECURITY |
| | ASSOCIATED WHEN THESE DOORS OPEN. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |