Plan Review Notes
Plan Review Notes For Permit 01071349
Permit Number 01071349
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-12-31 00:00:001) ATRIUM NOTES SECTION A1.1 INDICATES
 THAT THE ATRIUM SMOKE EXHAUST WILL
 BE TESTED BY A THIRD PARTY PRIOR TO
 ISSUANCE OF FINAL CERTIFICATE. PLEASE
 BE ADVISED THAT THE ATRIUM SYSTEM WILL
 BE TESTED WITH CITY OFFICIALS AFTER
 BEING NOTIFIED BY THE CONTRACTOR. PLEASE
 PROVIDE TESTING REQUIREMENTS FOR THE
 ATRIUM SYSTEM ON THE PLANS.
 2) ALSO NO DETAILS PROVIDED ON THE
 LOCATION, TYPE, OR IDENTITY OF THE
 FIREFIGHTER SMOKE EXHAUST PANEL
 REQUIRED PER NFPA 101, THE LIFE SAFETY
 CODE, SECTION 6-2.2.3.5, SECTION (G)
 3) THE NOTES REGARDING THE STOVE AND
 ASSOCIATED EQUIPMENT WILL PROBABLY NOT
 BE ALLOWED. ALL OF THE REQUIREMENTS OF
 NFPA 96 MUST BE MET SINCE THE
 RESIDENTIAL STOVE WILL BE LOCATED IN
 A COMMERCIAL BUILDING.
 4) HOW DOES THE ATRIUM SMOKE EXHAUST
 WORK SHOULD LOSS OF POWER OCCURS.
 5) THE FIRE DEPARTMENT CONNECTION FOR
 THE SPRINKLER SYSTEM MUST FACE TOWARDS
 THE FIRE HYDRANT AND NOT AWAY FROM IT.
 6) PLEASE INDCIATE NUMBER OF AIR
 CHANGES FOR ATRIUM SMOKE EXHAUST SYSTEM
 AND ANY ALL DEVICES THAT WILL ACTIVATE
 IT.
 7) SINCE DOORS OPEN FOR MAKE-UP AIR
 ARE THERE ANY PROBLEMS WITH SECURITY
 ASSOCIATED WHEN THESE DOORS OPEN.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910