Plan Review Notes
Plan Review Notes For Permit 01071349
Permit Number 01071349
Review Stop P
Sequence Number 2
Notes
Date Text
2001-12-08 00:00:00DENIED
 REFERENCE: SPC-94 - SMC-97 - FACBC-97
  
 1) SHT A-5.1, ENLARGED TOILET PLAN 1ST
 FLOOR. INSIDE DEPTH OF STALL TO BE 5'9"
 BUT IT SHOWS 5'9" TO OUTSIDE OF STALL.
 2) WATER HEATER #2. RESPONSE ACKNOWLEDG-
 ED BUT A PERMINATE SHIPS LADDER IS STILL
 REQUIRED. ALSO PER SMC-97 SEC 304.4.1,
 A LEVEL WORKING PLATFORM EXTENDING 30"
 FROM BASE OF EQUIPMENT AND A 36" HIGH
 WORKING SPACE IS REQUIRED AT THE CONTROL
 SIDE OF EQUIPMENT. ACCESS PANEL SHALL
 COMPLY WITH SMC SEC 304.4.1
 3) WATER HEATER #2. PER MODEL COUNTYWIDE
 AMENDMENTS TO THE STANDARD MECHANICAL
 CODE SEC 304.4.2, A DISCONNECT SWITCH, A
 SERVICE OUTLET CONVIENT TO EQUIPMENT, &
 A LIGHT LOCATED ON THE SERVICE SIDE OF
 THE EQUIPMENT WHICH IS CONTROLLED AT THE
 ACCESS.
 4) SHT P.08 NOTE #16 AIR CHAMBERS SHALL
 COMPLY WITH PDI-WH 201, SEE ATTACHED
 SHEET FOR APPROVED METHOD OF RECHARGING.
 EITHER REMOVE ALL AIR CHAMBERS OR COMPLY
 WITH ACCESS AND RECHARGEABILITY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377