| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SMC-97 - FACBC-97 | | | | | | 1) SHT A-5.1, ENLARGED TOILET PLAN 1ST | | | FLOOR. INSIDE DEPTH OF STALL TO BE 5'9" | | | BUT IT SHOWS 5'9" TO OUTSIDE OF STALL. | | | 2) WATER HEATER #2. RESPONSE ACKNOWLEDG- | | | ED BUT A PERMINATE SHIPS LADDER IS STILL | | | REQUIRED. ALSO PER SMC-97 SEC 304.4.1, | | | A LEVEL WORKING PLATFORM EXTENDING 30" | | | FROM BASE OF EQUIPMENT AND A 36" HIGH | | | WORKING SPACE IS REQUIRED AT THE CONTROL | | | SIDE OF EQUIPMENT. ACCESS PANEL SHALL | | | COMPLY WITH SMC SEC 304.4.1 | | | 3) WATER HEATER #2. PER MODEL COUNTYWIDE | | | AMENDMENTS TO THE STANDARD MECHANICAL | | | CODE SEC 304.4.2, A DISCONNECT SWITCH, A | | | SERVICE OUTLET CONVIENT TO EQUIPMENT, & | | | A LIGHT LOCATED ON THE SERVICE SIDE OF | | | THE EQUIPMENT WHICH IS CONTROLLED AT THE | | | ACCESS. | | | 4) SHT P.08 NOTE #16 AIR CHAMBERS SHALL | | | COMPLY WITH PDI-WH 201, SEE ATTACHED | | | SHEET FOR APPROVED METHOD OF RECHARGING. | | | EITHER REMOVE ALL AIR CHAMBERS OR COMPLY | | | WITH ACCESS AND RECHARGEABILITY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|