Plan Review Notes
Plan Review Notes For Permit 01071349
Permit Number 01071349
Review Stop M
Sequence Number 2
Notes
Date Text
2001-12-08 00:00:00 
 PROVISO:
  
 AIR BALANCE SCHEDULE DOES NOT INCLUDE
 CALCULATIONS FOR "EMERGENCY EXHAUST"
 FOR EXHAUST FAN #12, FOR OPEN STAIRWAY.
  
  
 CONDENSER UNIT RACK SHALL BE A MINIMUM
 OF 18" BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL. (COUNTY
 WIDE AMENDMENTS 1997 SMC 304.2.5)
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 AND FIRE SUPRESSION, SUBMIT PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.