| 2001-12-08 00:00:00 | | | | PROVISO: | | | | | | AIR BALANCE SCHEDULE DOES NOT INCLUDE | | | CALCULATIONS FOR "EMERGENCY EXHAUST" | | | FOR EXHAUST FAN #12, FOR OPEN STAIRWAY. | | | | | | | | | CONDENSER UNIT RACK SHALL BE A MINIMUM | | | OF 18" BETWEEN THE ROOF SURFACE AND THE | | | BOTTOM OF THE SUPPORT RAIL. (COUNTY | | | WIDE AMENDMENTS 1997 SMC 304.2.5) | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | AND FIRE SUPRESSION, SUBMIT PLANS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|