| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON THE | | | BUILDING NOT THE PLANS. | | | 2) A KNOX-BOX WILL BE REQUIRED FOR | | | FIRE RESCUE ACCESS. | | | 3) ALL OUTSIDE STEPS AND SURFACES ARE | | | TO BE SLIP RESISTANT. | | | 4) A STOVE IS NOTED IN THE PANTRY. | | | PLEASE INDICATE WHAT THE STOVE WILL BE | | | USED FOR. ANY COOKING THAT PRODUCES | | | SMOKE OR GREASE LADEN VAPORS MUST BE | | | PROTECTED BY A HOOD,DUCT, AND | | | EXTINGUISHING SYSTEM. PLEASE EXPLAIN. | | | 5) PLEASE EXPLAIN NOTES ON DOOR NOTES | | | "EXIT DOORS CONNECTED TO SECURITY | | | SYSTEM". | | | 6) STORAGE # 1, 107 IS LOCATED ADJACENT | | | TO AN EXIT. THIS AREA CANNOT INTERFERE | | | WITH ACCESS TO THE EXIT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|