2001-12-11 00:00:00BUILDING PLAN EVIEW
 PERMIT # 01071349
 621 CLEARWATER PARK RD
 CONT: LCI CONSTRUCTION
 ARCH: BEHAR, FONT & PARTNERS
 TEL: (305) 740-5442
  
 SBC= STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- COMMENT IS NOT FROM PREVIOUS REVIEW:
 THE OPEN STAIRWELL IN THE CENTER OF THE
 BUILDING IS BEING CONSIDERED AS A ATRIUM
 RATHER THAN A OPEN STAIRWAY. A OPEN
 STAIRWAY CAN ONLY COMMUNICATE BETWEEN
 2 FLOORS.
 SECTION 414.2 WILL REQUIRE A SMOKE
 EXHAUST SYSTEM. SUCH SYSTEMS SHALL
 EXHAUST 40,000 CFM.
  
 PLANS NEED TO BE ASSESSED BY PALM BEACH
 COUNTY BUILDING DEPART FOR COUNTY IMPACT
 FEES.
  
 RADON FEES TO BE PAID TO CITY,$212.37.