| Date |
Text |
| 2001-08-08 00:00:00 | DENIED; |
| | |
| | 1.PAGE C-5 BACKFLOW PREVENTER REQUIRED |
| | ON WATER SERVICE TO BUILDING. ALSO IF |
| | IRRIGATION SYSTEM IS TO USE CITY WATER |
| | PROTECTION IS REQUIRED AND SHALL BE |
| | INSTALLED BY THE PLUMBING CONTRACTOR. |
| | 2.PAGE A-5.1 (ENLARGED TOILET PLAN 1 FL) |
| | HANDICAP STALLS, DOOR CANNOT SWING |
| | INTO CLEAR FLOOR SPACE OF THE LAV. |
| | FACBC 4.22.2. INSIDE DEPTH SHALL BE |
| | 5' 9" FOR THE STALLS SEC.4.17.3. |
| | 3.ELEVATION 1 HANDICAP TOILET |
| | MESSUREMENTS OFF WALLS IS 18" NOT 19" |
| | SEE FIG.30. |
| | 4.GENERAL NOTE #1 "ALL WALLS IN REST- |
| | ROOMS TO BE DRYWALL AND PAINT". |
| | ELEVATIONS SHOW TILE. PLEASE CLARIFY. |
| | 5.PAGE A-5.2 ELEVATION 3 SAME AS PLAN |
| | REVIEW NOTE #3. |
| | 6.HANDICAP URINAL SHALL COMPLY WITH |
| | FACBC 4.18.3. NO MEASUREMENT GIVEN |
| | FOR URINALS. |
| | 7.2ND AND 3RD FLOOR HANDICAP STALLS MEN |
| | AND WEMANS INSIDE DIAMENTION SHALL BE |
| | 5'-9" SEC.4.17.3. |
| | 8.PAGEA-5.2.1 SHOWER SHALL COMPLY WITH |
| | SEC.4.21.3 AND FIG. 36. |
| | 9.PAGE A-5.4.1 LOUNGE SINK SHALL COMPLY |
| | WITH 4.24.2 34" HIGH. |
| | 10.SHOW COMPLIANCE WITH 94 SPC TABLE 407 |
| | FOR MINIMUM PLUMBING FIXTURES SHOW |
| | CALKULATIONS DRINKING FOUNTAIN |
| | REQUIRED ON FIRST FLOOR. |
| | 11.P-6 CONDENSATE ISOMETRIC DRAINS |
| | SHOULD BE VENTED THOUGH THE ROOF. |
| | 12.WATER HEATER # 2 SHALL BE READILY |
| | ACCESSIBLE. INSTALL ON FINISH FLOOR |
| | OR INSTALL A FIXED SHIPS LADDER NEXT |
| | TO HEATER. SPC 501.7 AND READILY |
| | ACCESSIBLE DEFINITION CHAPTER 2. |
| | 13.PAGE P.08 NOTE 16 AIR CHAMBERS SHALL |
| | BE APPROVED ENGINEERED WATER HAMMER |
| | ARRESTERS AND SHALL COMPLY WITH SEC. |
| | 607.8.2 AND 607.8.3 AND INSTALLED PER |
| | MANUFACTOR'S RECOMENDATIONS. |
| | |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 659-8096 EXT.8369 |