| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-16 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.PLEASE CLARFIY PLAN SHEET NOTES ON | | | THE REFRIGERANT SHAFTS, ARE THEY | | | BOTH VENTED?ON PLAN SHEETS M.02 | | | AND M.03 THE NOTES CHANGE AS DO THE | | | SHAFTS.PLEASE PROVIDE DETAIL OF | | | VENTED SHAFT ENCLOSURES AND ACCESS | | | DOORS PENETRATING FIRE RATED WALLS. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULETO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | | | | NOTE:PLAN SHEET M.06 DETAIL 8, 18" | | | MINIMUM FROM ROOF SURFACE TO THE | | | BOTTOM OF THE SUPPORT RAIL AS | | | PER AMENDED 1997 304.2.5. | | | | | | FAN SHUTDOWN BY DUCT SMOKE | | | DETECTOR WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS (NFPA 90A 4-4.4.3). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT 8388. |
|