| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-06 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER SYSTEM DRAWINGS. | | | 3) THE SIAMESE CONNECTION SHOWN ON | | | THE DRAWINGS IS NOT IN AN ACCEPTABLE | | | LOCATION. THE HOSE WILL KINK AND | | | WILL REDUCE PRESSURE. THIS CONNECTION | | | IS TO BE WITHIN 150 FEET OF A FIRE | | | HYDRANT. | | | 4) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | 5) PLEASE EXPLAIN USE OF OPEN STAIRS | | | AND WHAT FIRE PROTECTION FEATURES ARE | | | PLANNED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|