Plan Review Notes
Plan Review Notes For Permit 01071349
Permit Number 01071349
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-06 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER SYSTEM DRAWINGS.
 3) THE SIAMESE CONNECTION SHOWN ON
 THE DRAWINGS IS NOT IN AN ACCEPTABLE
 LOCATION. THE HOSE WILL KINK AND
 WILL REDUCE PRESSURE. THIS CONNECTION
 IS TO BE WITHIN 150 FEET OF A FIRE
 HYDRANT.
 4) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 5) PLEASE EXPLAIN USE OF OPEN STAIRS
 AND WHAT FIRE PROTECTION FEATURES ARE
 PLANNED.
  