| Date |
Text |
| 2001-08-03 00:00:00 | FAILED: |
| | 1. ALL DRIVEWAYS ALONG CITY'S R.O.W |
| | SHOULD BE CONSTRUCTED PER CITY STANDARD. |
| | SEE ATTACHED |
| | 2. ALL OFF-STREET PARKING STALLS SHOULD |
| | BE PAINTED WITH DOUBLE 4" WIDE PER CITY |
| | REQUIREMENT. |
| | 3. SHEET A-1.0 (ARCHITECTURAL) SHOWS |
| | DUMPSTER 13'-10" BY 13'-10", SHEET A-8.1 |
| | (ARCHITECTURAL) SHOWS 13'-4" BY 13'-4", |
| | PLEASE VERIFY.NOTE THAT CITY REQUIRES |
| | DUMPSTER TO BE 12'-0" DEEP WITH 12'-6" |
| | OPENING BETWEENTHE GATE POSTS. |
| | THE 2 1/2" CONCRETE FILLED PIPE SHOULD |
| | BE LOCATED 18" FROM THE BACK WALL(A 10' |
| | PRECAST WHEELSTOP COULD BE USED ALSO). |
| | 4. PLEASE VERIFY IF THE 249'-18" R.C.P |
| | NEEDS TO BE SHIFTED TO WEST IN ORDER TO |
| | PROVIDE ADEQUTE SPACE FOR THE PROPOSED |
| | A1-4' M.H NEXT TO EXISTING CATCH BASIN |
| | IN CLEARWATER PARK ROAD. |
| | 5. A RPZ BACKFLOW PREVENTER WILL NEED TO |
| | BE INSTALLED AT THE WATER METER ON |
| | PRIVETE PROPERTY. ALL BACKFLOW |
| | PREVENTERS SHALL BE COMPLETELY HIDDEN |
| | FROM VIEW WITH SHRUB. |
| | 6. A SEPARATE IRRIGATION METER IS |
| | SUGGESTED.A PROPER BACKFLOW PREVENTER |
| | WILL NEED TO BE INSTALLED ON THIS LINE. |
| | 7. ANY WORK WITHIN PUBLIC R.O.W WILL |
| | REQUIRE A SEPARATE PERMIT FROM CITY |
| | ENGINEER'S OFFICE , 659-8040. |
| | ANY NEW CONNECTION TO CITY SERVICES WILL |
| | REQUIRE A SEPARATE PERMIT FROM PUBLIC |
| | UTILITIES ENGINEERING SERVICES |
| | DEPARTMENT, 659-8040. |
| | 8. PLEASE PROVIDE PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE, |
| | IT SHOULD BE SIGNED AND SEALED BY THE |
| | DESIGN ENGINEER.THIS DATA WILL BE USED |
| | TO CALCULATE THE STORM CHARGES TO THE |
| | PROPERTY. |
| | |
| | IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |