2001-08-16 00:00:00***************** UNSAT **************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% (LIGHTING ETC. PER 230-42
 AND 215-3.
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IN OFFICES NEED TO MEET LOCAL CODE
 210-50. EACH 12' OF WALL SPACE. PLEASE
 NOTE THAT SOME OFFICES SEEM TO EXCEED
 12' SPACING.
  
 3)NOTE:PLEASE VERIFY FIRE PUMP AND/OR
 REQUIREMENTS. IF THERE IS GOING TO BE
 A FIRE PUMP? THEN PLEASE SHOW ON ELECTRI
 CAL RISER DIAGRAM WITH OCP/DISC/ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  