| Plan Review Notes For Permit 01071349 |
| Permit Number |
01071349 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-16 00:00:00 | ***************** UNSAT ************** | | | | | | 1) NOTE: PLEASE SHOW ALL CONTINUOUS | | | LOADS AT 125% (LIGHTING ETC. PER 230-42 | | | AND 215-3. | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IN OFFICES NEED TO MEET LOCAL CODE | | | 210-50. EACH 12' OF WALL SPACE. PLEASE | | | NOTE THAT SOME OFFICES SEEM TO EXCEED | | | 12' SPACING. | | | | | | 3)NOTE:PLEASE VERIFY FIRE PUMP AND/OR | | | REQUIREMENTS. IF THERE IS GOING TO BE | | | A FIRE PUMP? THEN PLEASE SHOW ON ELECTRI | | | CAL RISER DIAGRAM WITH OCP/DISC/ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|