2001-08-21 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01071349
 621 CLEARWATER PARK RD
 CONT: LCI CONSTRUCTION
 TEL:659-5111
 ARCH: BEHAR, FONT & PARTNERS
 TEL: (305) 740-5442
  
 SBC= STANDARD BUILDING CODE
 SBC*=STANDARD BUILDING CODE AMENDMENTS
  
 1)-SBC* 1804.2.7.2 SOILS REPORT GIVING
 THE MINIMUM BEARING VALUE.
  
 2)- SHEET S-10 FOUNDATION NOTES #3 PILE
 CAPACITY,16" PILE DIA. VS. 45' PILE
 LENGTH. SEE SBC 1809.2.2. DIMINSIONS
 AS TO SUPERVISION THAT WILL BE REQUIRED.
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, 1809.2.3. SHOW COMPLIANCE
 THROUGH METHOD IN (1809.2.3.1 OR
 1809.2.3.2.)
  
 4)- SHOW COMPLIANCE WITH SBC 1809.2.4
 CONCRETE PILE W/ REINFORCING, 4#7'S
 VERTICALLY FULL LENGTH& #3 TIES @ 12"OC
  
 5)- SHEET S-10 PILE CAP IMBEDMENT SEE
 SBC 1805.10.1
  
 6)- SBC T 600 TYPE OF BUILDING?
  
 7)- SBC TABLE 600 EXTERIOR WALLS NORTH
 SOUTH WALLS, OVER ALLOWABLE OPENING
 SIZES OVER 10' TO 20', 20% ALLOWABLE
 OPENINGS, OPENINGS ARE LIMITED TO A
 PERCENTAGE OF THE WALL AREA. THE WALL
 AREA IS CONSIDERED TO INCLUDE THE AREA
 FROM FLOOR LEVEL TO THE CEILING OF EACH
 STORY.
  
 8)- SBC 104.2.2.PRODUCT APPROVALS ARE RE
 QUIRED FOR EACH SET OF PLANS.
  
 9)- 1606.2.6.2COMPONENTS & CLADDING SHOW
 PRODUCT APPROVAL FOR WIND FOR THE ROOF
 HATCH.
  
 10)- SHEET A-1.4 THE DETAIL FORTHE ROOF
 OVER THE ELEVATOR SHAFT & OPEN STAIRWELL
 HAVE A PITCHED ROOF?
  
 11)- A-1.1 STORAGE ROOM #119 DOESN'T
 MEET THE REQUIREMENTS OF SBC 1027.1.1
 FOR SINGLE EXIT STORAGE WHEN THE FOLDING
 PARTITION FOR THE MEETING ROOM IS IN USE
  
  
 12)-PLEASE PROVIDE THE PRECASR JOIST LAY
 OUT AS WELL AS THE STEEL STAIR AND CALCU
 LATIONS.
  
 13)-SHEET A-8.4 ADD INFORMATION REQUIRED
 TERRACE DETAIL 7 & 8, MANUFACTURES SPEC-
 IFICATIONS & TEST REPORRTS INDICATING
 COMPLIANCE WITH SBC 1503.3.2/1503.4.12.
  
 14)- SHEET A-4.2.1 SEC @ STAIR 1 THE
 GUARDRAIL IS 42" HIGH, THE HANDRAIL IS
 ONLY 34" HIGH, SBC 1015.3 OPEN GAURD-
 RAILS SHALL HAVE INTERMEDIATE RAILS OR
 ORNAMENTAL PATTERNS SUCH THAT A 4" DIA.
 SPHERE CAN NOT PASS THROUGH ANY OPENING.
  
 15)- SHEET A-4.12 SBC 1814.2.4WALL FLOOR
 JOINTS & PENETRATIONS SHALL BE MADE
 WATERTIGHT USING APPROVED METHODS & MATE
 RIALS.
  
 16)- SHEET A-8.3 DEPICTS DETAILS 7-9
 WALL VENNEERS, AS PER MANUFACTURES SPEC?
 SBC 1403.2.5 REQUIREMENTS FOR ATTCHMENT.
  
 17)- INTERIOR FINISH SCHEDULE PER SBC
 TABLE 803.3 FLAME SPREAD/ SMOKE DEVELOP-
 MENT.
 PLAN REVIEW
 JIM WIMER
 (561) 659-8096 X 8412