2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE P-4, WATER ISOMETRIC DIAGRAM.
 AIR CHAMBERS ARE A "TEMPORY FIX" AND ARE
 IMPRACTICAL AND SERVE NOT PURPOSE. IF
 INSTALLED THEY WILL HAVE TO BE RECHARG-
 ABLE PER WH-PDI 201 WITH A SHUT OFF
 VALVE, A DRAIN VALVE AND AN AIR INTAKE
 VALVE AT THE TOP. WATER HAMMER ARRESTORS
 SHALL BE LOCATED PER WH-PDI 201 AND MAN-
 UFACTURE INSTALLATION INSTRUCTIONS NOT
 AT THE TOP OF DROP AS SHOWN ON PLANS.
 PLEASE SHOW PROPER LOCATION OF WATER
 HAMMER ARRESTORS ON WATER ISOMETRIC.
  