| Notes |
| Date |
Text |
| 2001-09-28 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE P-4, WATER ISOMETRIC DIAGRAM. | | | AIR CHAMBERS ARE A "TEMPORY FIX" AND ARE | | | IMPRACTICAL AND SERVE NOT PURPOSE. IF | | | INSTALLED THEY WILL HAVE TO BE RECHARG- | | | ABLE PER WH-PDI 201 WITH A SHUT OFF | | | VALVE, A DRAIN VALVE AND AN AIR INTAKE | | | VALVE AT THE TOP. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED PER WH-PDI 201 AND MAN- | | | UFACTURE INSTALLATION INSTRUCTIONS NOT | | | AT THE TOP OF DROP AS SHOWN ON PLANS. | | | PLEASE SHOW PROPER LOCATION OF WATER | | | HAMMER ARRESTORS ON WATER ISOMETRIC. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|