| 2001-09-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01071328 |
| | 2801 OKEECHOBEE BLVD. |
| | TEL: (954) 781 2120 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS TO 1997 STANDARD BUILD- |
| | ING CODE |
| | FL ACCES CODE= FLORIDA ACCESSIBILITY |
| | CODE 1997 EDITION |
| | |
| | 1)- A COMMENT FROM PREVIOUS PLAN REVIEW |
| | IS ABOUT THE "OMEGALITE PANELS" REGARD- |
| | ING FIRE RATING IN A FIRE DISTRICT, WHAT |
| | IS NOT CLEAR ON SHEET S-6 DETAILS 4&5 |
| | THE COMPOSITE SHEET IS MADE OF? THE DE- |
| | TAILS SHOW THAT IT HAS A PLYWOOD BACKING |
| | WE ARE TAKING THAT THIS IS NOT PART OF |
| | THE COMPOSITE PANEL BUT A BACKING MATER- |
| | IAL TO ATTACH THE PANELS TO. SBC FI02.1 |
| | & F102.7 ARE FOR ARCHITECTURAL TRIM LOCA |
| | TED IN A FIRE DISTRICT,NONCOMBUSTIBLE OR |
| | FIRE RETARDANT TREATED PLYWOOD. |
| | |
| | 2)-THE TEST THAT ARE INDICATED ARE FOR |
| | INTERIOR FLAME SPREAD AND SMOKE DEVELOP- |
| | MENT, BY DEFINITION NONCOMBUSTIBLE CAN |
| | BE TESTED (2) DIFFERENT WAYS,DEPENDING |
| | ON THE THICKNESS OF THE MATERIAL THERE |
| | HAS BEEN NO SPECS ON THIS MATERIAL AS TO |
| | THICKNESS NOR THE FASTENING OF THE |
| | SYSTEM TO WHATEVER MATERIAL THAT WILL BE |
| | SUPPORTING THE COMPOSITE PANELS.THE 2 |
| | METHOSOF TESTING ARE ASTM E 136 & |
| | ASTM E 84 WHEN THE MATERIALS HAVING A |
| | STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIALS AS DEFINED IN 1, WITH A SURFAC |
| | ING NOT MORE THAN 1/8" THICK AND A |
| | FLAMESPREAD RATING OF NOT MORE THAN 50 |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E 84 |
| | |
| | 3)-MISSING ARE PRODUCT APPROVAL REPORTS |
| | FOR THE OVERHEAD GARAGE DOORS, THE EXTER |
| | IOR DOOR 2ND FLOOR, AND THE ROOFING |
| | REPORT. THE CITY ACCEPTS SBCCI TESTING |
| | REPORTS & DADE COUNTY, (2) COPIES OF |
| | EACH REPORT.SBC 1606.2.6.2 |
| | |
| | 4)- S-6 DETAILS 4 & 5 WHAT IS THE MINI- |
| | MUM WORKING DEPTH FOR TAPCONS IN THE 2X8 |
| | PT FOR CONCRETE? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |