| Plan Review Notes For Permit 01071328 |
| Permit Number |
01071328 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-13 00:00:00 | DENIED; | | | 1.P-1 SEWER REQUIRES CLEANOUTS EVERY | | | 80 FEET. 94 SPC SEC.710.2.4. | | | 2.SHOW STORM WATER CALKULATIONS. USE 4.5 | | | INCHES OF RAIN PER FIG. 1108.4 AND ADD | | | 1/2 OF THE PARAPIT WALL IN CALKS. | | | 3.CANOPY ROOF DRAIN SHALL DRAIN TO | | | STORM SEWER SYSTEM. SPC 1101.2. | | | 4.PAGE P-5 NOTE 8 VI NO DRAWING FOR | | | COMPRESSED AIR OR OIL PIPING. PLEASE | | | SUBMIT. | | | 5.APPROVED ENGINEERED MECHANICAL WATER | | | HAMMER ARRESTERS SHALL BE SIZED PER | | | SPC SEC. 607.8.2 AND 607.8.3 AND | | | INSTALLED PER MANUFACTORS SPECIFICA- | | | TIONS. | | | 6.SHOW ON DRAWING COMPLIANCE TO MINIMUM | | | PLUMBING FACILITIES PER. 94 SPC TABLE | | | 407. | | | 7.LOUNGE SINK SHALL COMPLY WITH FACBC | | | 4.24.2, 4.24.4,4.24.5,AND 4024.7. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|