Plan Review Notes
Plan Review Notes For Permit 01071328
Permit Number 01071328
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-13 00:00:00DENIED;
 1.P-1 SEWER REQUIRES CLEANOUTS EVERY
 80 FEET. 94 SPC SEC.710.2.4.
 2.SHOW STORM WATER CALKULATIONS. USE 4.5
 INCHES OF RAIN PER FIG. 1108.4 AND ADD
 1/2 OF THE PARAPIT WALL IN CALKS.
 3.CANOPY ROOF DRAIN SHALL DRAIN TO
 STORM SEWER SYSTEM. SPC 1101.2.
 4.PAGE P-5 NOTE 8 VI NO DRAWING FOR
 COMPRESSED AIR OR OIL PIPING. PLEASE
 SUBMIT.
 5.APPROVED ENGINEERED MECHANICAL WATER
 HAMMER ARRESTERS SHALL BE SIZED PER
 SPC SEC. 607.8.2 AND 607.8.3 AND
 INSTALLED PER MANUFACTORS SPECIFICA-
 TIONS.
 6.SHOW ON DRAWING COMPLIANCE TO MINIMUM
 PLUMBING FACILITIES PER. 94 SPC TABLE
 407.
 7.LOUNGE SINK SHALL COMPLY WITH FACBC
 4.24.2, 4.24.4,4.24.5,AND 4024.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369