Plan Review Notes
Plan Review Notes For Permit 01071328
Permit Number 01071328
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING OUTLETS FOR
 SHOW ROOM WINDOWS PER 210-62
  
 20NOTE: PLEASE NOTE THAT OANS ARE SHOW-
 -ING THE SAME WIRE COUNT FROM GUTTER TO
 MAINS AND FROM MAINS TO PANELS. PLEASE
 NOTE THAT WIRE SCHEDULE IS SHOWING AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 GUTTER TO FIRST MEANS OS DISCONNECT.
 THIS MEANS THE GROUND WOULD BE PARALLEL-
 ING THE NEUTRAL. NOT PERMITTED PER 250
 OF NEC.
  
 3)NOTE: PLEASE CLARIFY THAT MAIN 2 OF 5
 SHOWN AS 200AMPS W/ 4/0 CONDUCTORS AND
 MAIN 4 OF 5 SHOWN AS 200AMPS ALSO BUT
 WITH 3/0`S?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 NOTES 1&2 FOR REVIEW. NOTE 3 WAS JUST
 FOR CLARIFICATION. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372