| Plan Review Notes For Permit 01071328 |
| Permit Number |
01071328 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-08 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLETS FOR | | | SHOW ROOM WINDOWS PER 210-62 | | | | | | 20NOTE: PLEASE NOTE THAT OANS ARE SHOW- | | | -ING THE SAME WIRE COUNT FROM GUTTER TO | | | MAINS AND FROM MAINS TO PANELS. PLEASE | | | NOTE THAT WIRE SCHEDULE IS SHOWING AN | | | EQUIPMENT GROUNDING CONDUCTOR FROM | | | GUTTER TO FIRST MEANS OS DISCONNECT. | | | THIS MEANS THE GROUND WOULD BE PARALLEL- | | | ING THE NEUTRAL. NOT PERMITTED PER 250 | | | OF NEC. | | | | | | 3)NOTE: PLEASE CLARIFY THAT MAIN 2 OF 5 | | | SHOWN AS 200AMPS W/ 4/0 CONDUCTORS AND | | | MAIN 4 OF 5 SHOWN AS 200AMPS ALSO BUT | | | WITH 3/0`S? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | NOTES 1&2 FOR REVIEW. NOTE 3 WAS JUST | | | FOR CLARIFICATION. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|