| Date |
Text |
| 2001-08-13 00:00:00 | PLEASE PROVIDE A DIMENSIONED SITE PLAN |
| | SO THAT COMPLIANCE WITH SBC TABLE 600 |
| | MAY BE DETERMINED. |
| | |
| | CLEARLY SHOW THE MIXED OCCUPANCY |
| | SEPARATIONS FOR THE B, M, AND S (REPAIR |
| | GARAGE)SEE SBC 411.5, SBC 704.1. |
| | |
| | HOW WILL HANDICAP ACCESS TO THE LOUNGE |
| | FROM THE SHOWROOM BE ACCOMPLISHED?SEE |
| | FACBC 4.1.1. |
| | |
| | THERE ARE NO ROOF OVERFLOW SCUPPERS |
| | SHOWN FOR THE SERVICE / RECEPTION |
| | CANOPY.SEE SBC 1517.6.4.3. |
| | |
| | THE AREA SHOWN AS A "MEZZANINE" DOES NOT |
| | MEET THE CRITERIA OF SBC 503.2.3 AND |
| | THEREFORE MUST COMPLY WITH STORY |
| | REQUIREMENTS, AS TO EGRESS AND FIRE |
| | RATED SEPARATIONS.ALSO, SEE SBC |
| | F102.2.5 FOR FIRE RESISTANT |
| | CONSTRUCTION REQUIREMENTS FOR BUILDINGS |
| | LOCATED INSIDE THE DESIGNATED FIRE |
| | DISTRICT. |
| | |
| | PLEASE PROVIDE TEST DATA THAT THE |
| | "OMEGALITE PANELS" ARE LISTED AS |
| | NON-COMBUSTIBLE OR FIRE RETARDANT.SEE |
| | SBC F102.1 AND F102.7 |
| | |
| | PROVIDE SPECIFIC STRUCTURAL CONNECTION |
| | DETAILS FOR THE PANELS. |
| | |
| | THE STORE FRONT PRODUCT ACCEPTANCE |
| | REPORTS PROVIDED ARE EXPIRED AND HAVE |
| | SOME ILLEGIBLE PAGES. |
| | |
| | IMPACT FEES MUST BE PAID TO THE COUNTY |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED.CALL 561-233-5025 FOR MORE |
| | INFORMATION. |