Plan Review Notes
Plan Review Notes For Permit 01071328
Permit Number 01071328
Review Stop B
Sequence Number 1
Notes
Date Text
2001-08-13 00:00:00PLEASE PROVIDE A DIMENSIONED SITE PLAN
 SO THAT COMPLIANCE WITH SBC TABLE 600
 MAY BE DETERMINED.
  
 CLEARLY SHOW THE MIXED OCCUPANCY
 SEPARATIONS FOR THE B, M, AND S (REPAIR
 GARAGE)SEE SBC 411.5, SBC 704.1.
  
 HOW WILL HANDICAP ACCESS TO THE LOUNGE
 FROM THE SHOWROOM BE ACCOMPLISHED?SEE
 FACBC 4.1.1.
  
 THERE ARE NO ROOF OVERFLOW SCUPPERS
 SHOWN FOR THE SERVICE / RECEPTION
 CANOPY.SEE SBC 1517.6.4.3.
  
 THE AREA SHOWN AS A "MEZZANINE" DOES NOT
 MEET THE CRITERIA OF SBC 503.2.3 AND
 THEREFORE MUST COMPLY WITH STORY
 REQUIREMENTS, AS TO EGRESS AND FIRE
 RATED SEPARATIONS.ALSO, SEE SBC
 F102.2.5 FOR FIRE RESISTANT
 CONSTRUCTION REQUIREMENTS FOR BUILDINGS
 LOCATED INSIDE THE DESIGNATED FIRE
 DISTRICT.
  
 PLEASE PROVIDE TEST DATA THAT THE
 "OMEGALITE PANELS" ARE LISTED AS
 NON-COMBUSTIBLE OR FIRE RETARDANT.SEE
 SBC F102.1 AND F102.7
  
 PROVIDE SPECIFIC STRUCTURAL CONNECTION
 DETAILS FOR THE PANELS.
  
 THE STORE FRONT PRODUCT ACCEPTANCE
 REPORTS PROVIDED ARE EXPIRED AND HAVE
 SOME ILLEGIBLE PAGES.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED.CALL 561-233-5025 FOR MORE
 INFORMATION.