Plan Review Notes
Plan Review Notes For Permit 01071304
Permit Number 01071304
Review Stop P
Sequence Number 5
Notes
Date Text
2002-03-28 00:00:00DENIED
 REFERENCE: SPC-94-SGC-97- FACBC-97
  
 1) SHT P-1/P-3 DROP IN ICE BIN AND TWO
 COMP SINK SHALL BE INDIRECT WASTE TO
 FLOOR SINK. SEC 804.1
 2) SHT P-4 WATER ISOMETRIC, WATER LINES
 CHANGED TO 3/4" AT DISHWASHING AREA BUT
 NOT ON WATER ISO.
 3) SHT P-4 WATER ISOMETRIC, WATER HEATER
 SHOWN CHANGED TO ROOF ON SHT P-2 BUT NOT
 ON WATER ISO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377