| Notes |
| Date |
Text |
| 2002-03-28 00:00:00 | DENIED | | | REFERENCE: SPC-94-SGC-97- FACBC-97 | | | | | | 1) SHT P-1/P-3 DROP IN ICE BIN AND TWO | | | COMP SINK SHALL BE INDIRECT WASTE TO | | | FLOOR SINK. SEC 804.1 | | | 2) SHT P-4 WATER ISOMETRIC, WATER LINES | | | CHANGED TO 3/4" AT DISHWASHING AREA BUT | | | NOT ON WATER ISO. | | | 3) SHT P-4 WATER ISOMETRIC, WATER HEATER | | | SHOWN CHANGED TO ROOF ON SHT P-2 BUT NOT | | | ON WATER ISO. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|