2002-03-14 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE PER REVIEW OF PLANS
 W/ FIELD INSPECTOR, IF OUTSIDE LTS ARE
 SHOWN ON PLANS, THEN SOME SORT OF OUT-
 -DOOR FIXTURES MUST BE INSTALLED.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET LOCAL AMENDMENTS 210-50 (UPSTAIRS)
  
 3)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL SCHEDULES AND LOADS CARRIED
 OVER PANEL "A/C".
  
 4)NOTE: PLEASE CLARIFY LOADS SHOWN ON
 PANEL A/C., SHOWN ABOVE 600A RATING OF
 EQUIPMENT.
  
 5)NOTE: PLEASE NOTE THAT SOME CIRCUIT
 #`S ON PLANS DO NOT CORRELATE WITH
 PANEL SCHEDULES.
  
 6)NOTE:, PLEASE SHOW LOAD CALCUALTIONS,
 TO INCLUDE WATTS PER SQ FT/RECEPTS
 220-3, 220-13 ETC.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS,PLEASE CALL.
  