| Plan Review Notes For Permit 01071304 |
| Permit Number |
01071304 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-14 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE PER REVIEW OF PLANS | | | W/ FIELD INSPECTOR, IF OUTSIDE LTS ARE | | | SHOWN ON PLANS, THEN SOME SORT OF OUT- | | | -DOOR FIXTURES MUST BE INSTALLED. | | | | | | 2)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL AMENDMENTS 210-50 (UPSTAIRS) | | | | | | 3)NOTE: PLEASE CORRELATE LOADS SHOWN | | | ON PANEL SCHEDULES AND LOADS CARRIED | | | OVER PANEL "A/C". | | | | | | 4)NOTE: PLEASE CLARIFY LOADS SHOWN ON | | | PANEL A/C., SHOWN ABOVE 600A RATING OF | | | EQUIPMENT. | | | | | | 5)NOTE: PLEASE NOTE THAT SOME CIRCUIT | | | #`S ON PLANS DO NOT CORRELATE WITH | | | PANEL SCHEDULES. | | | | | | 6)NOTE:, PLEASE SHOW LOAD CALCUALTIONS, | | | TO INCLUDE WATTS PER SQ FT/RECEPTS | | | 220-3, 220-13 ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|