| 2001-09-22 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | PREVIOUS NOTES NOT ADDRESSED, PLUS MORE. |
| | (1) SHT S-2,A-1.4 SHOW LOCATION OF ROOF |
| | DRAINS,SCUPPERS. SIZE WITH CALCULATIONS |
| | SPC-94 SEC 1108,1109. |
| | (2) SHT P-1 RM #107 SHOWS,JOSAM 6052OA? |
| | SHT A-1 SHOWS BIG DIPPER VAULT? |
| | LOCAL ORDINANCE #2938-96 REQUIRES A MIN. |
| | 750 GAL GREASE,TANK LOCATED OUTSIDE OF |
| | BUILDING, SIZED BY REG SEWER TREATMENT |
| | PLANT, CONTACT ROD COMPO 561-837-4074. |
| | (3) SHT P-1 RM #107 NO DRAIN & H/C WATER |
| | FOR CAN WASH & JANITORS SINK. |
| | (4) SHT A 1.5,1ST FLR MEN & WOMEN'S REST |
| | RM'S, COMPLY W/FACBC-97,SEC 4.1.6 (1)(B) |
| | & 4.1.6.(2) PRIMARY FUNCITION, FOR NEW |
| | CONSTRUCTION, H/C ACCESSIBLE. |
| | (5) SHT SHT A-1.3 2ND FLR PRIVATE REST |
| | RM, TO COMPLY W/FACBC-97 SEC 4.1.3(11) |
| | TO BE ADAPTABLE FOR H/C. |
| | (6) SHT P-1,P-5,1ST & 2ND FLR (I/D) SAFE |
| | WASTE TO F/D OR F/S NOT APPROVED, SPC-94 |
| | SEC 802, FLR DRAIN IS FOR SPILLS &MOP |
| | AREA, FLR SINKS ARE FOR INDIRECT WASTE. |
| | (7) SHT P-3, 3 COMP SINKS, SEC 804.1 |
| | FOOD HANDLING, RINSE SINKS TO FLR SINKS |
| | (8) SHT P-1,COOLER CONDENSATE TO F/S. |
| | (9) SHT P-3,BAR EQUIPMENT DRAINS TO F/S. |
| | (10) SHT P-6,NOTE L, F REFERENCE TO AIR |
| | CHAMBERS, DELETE ,SEC 607.8.3 TO BE |
| | ACCESSIBLE & RECHARGEALE,IMPRACTICAL. |
| | (11) SHT P-4 WATER HAMMER ARRESTORS TO |
| | BE INSTALLED PER MFG INSTRUCTIONS FOR |
| | SIZE AND LOCATION, "NOT IN THE CEILING". |
| | (12) SHT P-4,P-6, GAS PERMIT APPLICATION |
| | REQUIRMENTS,ADDRESS PREVIOUS COMMENTS. |
| | (A) FPU DELIVERS .5# PSI, 12"TO 14" W/C. |
| | (B)TOTAL DEVELOPED LGTH IS CLOSER TO 60' |
| | (C) MANFACTURE SHEETS FOR ALL EQUIPMENT |
| | (D) EMERGENCY HOOD SOV,TO BE LOCATED |
| | CLOSE TO THE HOOD, W/MANUAL SOV UP |
| | STREAM OF THEEMERGENCY SOV, WITH A |
| | UNION DOWN STREAM. |
| | (E) TOTAL BTU'S NOT CORRECT,2 APPLIANCES |
| | LEFT OUT, "TOT. BTU'S 662K". |
| | END OF COMMENTSPAUL SCHMITZ |