| 2001-08-20 00:00:00 | DENIED; |
| | 1.PLANS TO BE REVIEW AND APPROVED BY THE |
| | HOTEL BUSINESS REGULATIONS. |
| | 2.GREASE TRAP, SIZE AND LOCATION TO BE |
| | APPROVED BY UTILTY DEPARTMENT CONTACT |
| | RODNEY COMPO AT 837-4074. |
| | 3.FLOOR SINKS ARE REQUIRED FOR ALL |
| | INDIRECT WASTES. |
| | 4.PAGE P-1 WALKIN COOLER CONDENSATE TO |
| | DISCHARGE INTO A FLOOR SINK, NOT SAFE- |
| | WASTED. |
| | 5.DISHWASHER TO DISCHARGE INTO A FLOOR |
| | SINK. FLOOR SINK WILL DISCHARGE TO |
| | SANITARY SEWER SYSTEM PER UTILITY |
| | ORD. |
| | 6.3 COMPARTMENT SINK TO DISCHARGE |
| | INDIRECTLY INTO A FLOOR SINK. SPC SEC. |
| | 804.1. |
| | 7.CAN WASH, JAN. SINK TO DISCHARGE TO |
| | GREASY WASTE NOT SANITARY. |
| | 8.BAR EQUIPMENT TO DISCHARGE INDIRECTLY |
| | INTO FLOOR SINKS. |
| | 9.PAGE P-4. TEMPERING VALVE REQUIRED AT |
| | AT WATER HEATER TO REDUCE THE TEMP. |
| | FROM 140F TO 110F FOR HAND SINKS AND |
| | LAVS. |
| | 10.WATER HEATER PAN DRAIN SHALL BE 1" |
| | PER.507.8.2. |
| | 11.MECHANICAL WATER HAMMER ARRESTERS TO |
| | BE SIZED BY THE ENGINEER AND INSTALL |
| | ED PER MANUFACTORS RECOMMENDATIONS. |
| | SEN. 607.8.2 AND 607.8.3. |
| | 12.AUTO. SHUTOFF FOR GAS EQUIPMENT |
| | SHOULD BE INSTALLED NEXT TO HOOD. |
| | BELOW THE CEILING WITH A MANUAL SHUT- |
| | OFF VALVE UP STREAM AND A UNION DOWN |
| | STREAM. |
| | 13.SHOW DIRT LEG. |
| | 14.FOLLOW ATTACHED FORM, HIGHLIGHTED |
| | ITEMS "GAS PERMIT APPLICATION |
| | REQUIREMENTS'. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 659-8096 EXT. 8369 |