Plan Review Notes
Plan Review Notes For Permit 01071304
Permit Number 01071304
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-20 00:00:00DENIED;
 1.PLANS TO BE REVIEW AND APPROVED BY THE
 HOTEL BUSINESS REGULATIONS.
 2.GREASE TRAP, SIZE AND LOCATION TO BE
 APPROVED BY UTILTY DEPARTMENT CONTACT
 RODNEY COMPO AT 837-4074.
 3.FLOOR SINKS ARE REQUIRED FOR ALL
 INDIRECT WASTES.
 4.PAGE P-1 WALKIN COOLER CONDENSATE TO
 DISCHARGE INTO A FLOOR SINK, NOT SAFE-
 WASTED.
 5.DISHWASHER TO DISCHARGE INTO A FLOOR
 SINK. FLOOR SINK WILL DISCHARGE TO
 SANITARY SEWER SYSTEM PER UTILITY
 ORD.
 6.3 COMPARTMENT SINK TO DISCHARGE
 INDIRECTLY INTO A FLOOR SINK. SPC SEC.
 804.1.
 7.CAN WASH, JAN. SINK TO DISCHARGE TO
 GREASY WASTE NOT SANITARY.
 8.BAR EQUIPMENT TO DISCHARGE INDIRECTLY
 INTO FLOOR SINKS.
 9.PAGE P-4. TEMPERING VALVE REQUIRED AT
 AT WATER HEATER TO REDUCE THE TEMP.
 FROM 140F TO 110F FOR HAND SINKS AND
 LAVS.
 10.WATER HEATER PAN DRAIN SHALL BE 1"
 PER.507.8.2.
 11.MECHANICAL WATER HAMMER ARRESTERS TO
 BE SIZED BY THE ENGINEER AND INSTALL
 ED PER MANUFACTORS RECOMMENDATIONS.
 SEN. 607.8.2 AND 607.8.3.
 12.AUTO. SHUTOFF FOR GAS EQUIPMENT
 SHOULD BE INSTALLED NEXT TO HOOD.
 BELOW THE CEILING WITH A MANUAL SHUT-
 OFF VALVE UP STREAM AND A UNION DOWN
 STREAM.
 13.SHOW DIRT LEG.
 14.FOLLOW ATTACHED FORM, HIGHLIGHTED
 ITEMS "GAS PERMIT APPLICATION
 REQUIREMENTS'.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369