| 2001-08-21 00:00:00 | ********************DENIED************** |
| | |
| | |
| | PLEASE SUBMIT THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | |
| | 1.PLAN A-1.3 INDICATES AC CHASE IS |
| | NON-RATED AS PER 1997 SMC 610.2 & |
| | 610.4, DUCTS EXTENDING THROUGH MORE |
| | THAN ONE FLOOR SHALL HAVE A SHAFT |
| | ENCLOSURE HAVING A FIRE FATING OF |
| | NOT LESS THAN 1 HOUR OR DUCTS |
| | PENETRATING ONLY 1 FLOOR MAY BE |
| | PROTECTED BY INSTALLING A LISTED |
| | FIRE DAMPER. ACCESS DOOR OR OTHER |
| | APPROVED MEANS OF ACCESS SHALL BE |
| | PROVIDED IN DUCTS TO PERMIT THE |
| | PROPER MAINTENANCE AND RESETTING OF |
| | EACH FIRE DAMPER.LOCATION AND |
| | INSTALLATION DETAILS OF EACH FIRE |
| | DOOR, DAMPER, CEILING DAMPER SHALL |
| | BE PROPERLY IDENTIFIED ON PLANS. |
| | |
| | 2.GREASE DUCT SHALL HAVE ADEQUATE |
| | CLEARANCE FOR INSPECTION OF WELDS |
| | AND FIREWRAP.CLEANOUTS ARE |
| | REQUIRED AT EACH CHANGE OF DIRECTION |
| | OR ANY PORTION OF DUCT THAT IS NOT |
| | ACCESSIBLE FROM THE DUCT INLET OR |
| | DISCHARGE. PLEASE SUBMIT PRODUCT |
| | APPROVAL FOR THE 3M FIREMASTER DUCT |
| | WRAP WITH MECH HOOD PERMIT |
| | APPLICATION. |
| | |
| | |
| | NOTE:ADDITIONAL PERMITS REQUIRED FOR |
| | HOOD, FIRE SUPRESSION AND WALK-IN |
| | COOLER/FREEZER.PLEASE SUBMIT |
| | PLANS AND MANUFACTURER SUBMITTAL |
| | DATA WITH PERMIT APPLICATION. |
| | |