2001-08-21 00:00:00********************DENIED**************
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.PLAN A-1.3 INDICATES AC CHASE IS
 NON-RATED AS PER 1997 SMC 610.2 &
 610.4, DUCTS EXTENDING THROUGH MORE
 THAN ONE FLOOR SHALL HAVE A SHAFT
 ENCLOSURE HAVING A FIRE FATING OF
 NOT LESS THAN 1 HOUR OR DUCTS
 PENETRATING ONLY 1 FLOOR MAY BE
 PROTECTED BY INSTALLING A LISTED
 FIRE DAMPER. ACCESS DOOR OR OTHER
 APPROVED MEANS OF ACCESS SHALL BE
 PROVIDED IN DUCTS TO PERMIT THE
 PROPER MAINTENANCE AND RESETTING OF
 EACH FIRE DAMPER.LOCATION AND
 INSTALLATION DETAILS OF EACH FIRE
 DOOR, DAMPER, CEILING DAMPER SHALL
 BE PROPERLY IDENTIFIED ON PLANS.
  
 2.GREASE DUCT SHALL HAVE ADEQUATE
 CLEARANCE FOR INSPECTION OF WELDS
 AND FIREWRAP.CLEANOUTS ARE
 REQUIRED AT EACH CHANGE OF DIRECTION
 OR ANY PORTION OF DUCT THAT IS NOT
 ACCESSIBLE FROM THE DUCT INLET OR
 DISCHARGE. PLEASE SUBMIT PRODUCT
 APPROVAL FOR THE 3M FIREMASTER DUCT
 WRAP WITH MECH HOOD PERMIT
 APPLICATION.
  
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER.PLEASE SUBMIT
 PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.