Plan Review Notes
Plan Review Notes For Permit 01071304
Permit Number 01071304
Review Stop B
Sequence Number 1
Notes
Date Text
2001-08-17 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 SO THAT COMPLIANCE WITH TABLE 600 MAY BE
 DETERMINED.
  
 THE CHANGE IN USE MAY BE SUBJECT TO
 IMPACT FEES.CONTACT PALM BEACH COUNTY
 FOR MORE INFORMATION, 233-5025, AND
 HAVE THE PERMIT PLANS STAMPED BY THAT
 OFFICE.
  
 THE $175000 DECLARED VALUATION APPEARS
 TOO LOW FOR THIS SCOPE OF WORK.PLEASE
 PROVIDE A SIGNED CONTRACT AND A
 DETAILED TAKEOFF TO JUSTIFY THE VALUE.
  
 SHEET A1.2, IT APPEARS THE FRONT DOORS
 WILL SWING OVER THE PUBLIC SIDEWALK.
 SEE SBC 3203.
  
 PROVIDE THE TEST REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING THAT
 DEMONSTRATE THEIR ABILITY TO RESIST THE
 DESIGN WINDLOADS.
  
 IT IS THE BUILDING OFFICIAL'S
 INTERPRETATION THAT ABOVE GRADE GLAZING
 BE MISSLE IMPACT RESISTANT AND SHUTTERS
 ARE NOT AN ACCEPTABLE SUBSTITUTE.SEE
 SBC 1606.4 AMENDED.
  
 THE USE OF A LIFT IN PLACE OF AN
 ELEVATOR MUST MEET THE CRITERIA OF
 FACBC 4.1.3, (5).
  
 SBC 1006.1.1 REQUIRES EGRESS STAIRS TO
 BE ENCLOSED IN FIRE RATED CONSTRUCTION.
  
 THE STAIRS MUST PROVIDE A PROTECTED
 EXITTO A PUBLIC PLACE.SEE SBC 1010.
  
 GIVEN THE CHANGE OF USE THE STAIRS
 SHOULD BROUGHT INTO COMPLIANCE WITH SBC
 1007.6.