| 2001-09-26 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SMC-97 |
| | 1) PAGES D-1/A-6 PROVIDE SANITARY RISER |
| | DIAGRAM AND WATER RISER DIAGRAM FOR NEW |
| | SINKS. |
| | 2) PAGES D-1/A-6 PLEASE PROVIDE INFOR- |
| | MATION FOR STEAM GENERATOR. WHAT IS THE |
| | STEAM FOR? PROVIDE PIPING INFORMATION. |
| | 3) PAGES D-1/A-7 RELOCATION OF WATER |
| | HEATER. PREVIOUS PLAN REVIEW NOT ADDRES- |
| | SED. PLEASE SHOW INFORMATION ON WORKING |
| | PLATFORM, LIGHT, WALKWAK TO HEATER (MIN- |
| | IMUM 24" WIDE) AND ACCESS SIZE. PER |
| | SMC-97 SEC 304.4, SPC-94 SEC 501.7. |
| | 4) PAGE A-7 PROVIDE DETAILS ON PAN, PAN |
| | DRAIN AND T&P DRAIN LINE FROM W/HEATER. |
| | SPC-94 SEC 507.8.1,2,2 AND 4. |
| | 5) PAGE A-3 PLEASE PROVIDE ROOF DRAIN |
| | CALCULATIONS FOR ROOF DRAIN PER SPC-94 |
| | SEC 1108. ALSO PROVIDE SECONDARY ROOF |
| | DRAIN CALCULATIONS USING SEC 1109. |
| | SHOW RISER DIAGRAMS FOR BOTH WITH ALL |
| | PIPE SIZES. |
| | 6) PAGE A-6 PREVIOUS COMMENTS #1 AND #2 |
| | FROM PLAN REVIEW DATED 8-9-01 WERE NOT |
| | ADDRESSED. PLEASE SHOW COMPLIANCE FOR |
| | DRESSING ROOMS PER FACBC SEC 4.35 THRU |
| | 4.35.5. ALSO SHOW COMPLIANCE FOR SHOWERS |
| | PER FACBC SEC 4.21 THRU 4.21.4 AND FIG. |
| | 35. |
| | 7) PAGE A-6 WATER RISER DIAGRAM. PLEASE |
| | LOCATE WATER HAMMER ARRESTORS PER MANU- |
| | FACTURES INSTALLATION INSTRUCTIONS AND |
| | WH-PDI 201, NOT AT TOP OF DROP AS SHOWN. |
| | 8) PAGE A-6 PLEASE PROVIDE CALCULATIONS |
| | FOR MINIMUM FIXTURES USING SPC-94 TABLE |
| | 407. SHOW DETAILS OF ALL RESTROOMS, GIVE |
| | ROOM DIMENTIONS ECT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |