Plan Review Notes
Plan Review Notes For Permit 01071242
Permit Number 01071242
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-26 00:00:001) EXHAUST FAN DOES NOT MEET MINIMUM
 AIR FLOW REQUIREMENTS. THE MINIMUM AIR
 FLOW SHALL NOT BE LESS THAN 1500 CFM
 PER MINUTE. PLEASE SEE NFPA 96, SECTION
 5-2.1
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497