2001-08-27 00:00:00CHECKLIST:
 1-PROPOSED BUILDING DOESN'T COMPLY WITH
 TABLE 600 OF SBC 1997. THE 2 BUILDINGS
 ARE TOO CLOSE TOGETHER. THEREFORE, THE
 PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 IS EXCEEDED.
 2-BATHROOM WINDOW DOESN'T PROVIDE THE
 MINIMUM REQUIRED VENTILATION BY SEC.
 1203.4.2 SBC 1997.
 -INCREASE WINDOW SIZE TO MEET THE MIN.
 REQUIREMENTS OR PROVIDE MECHANICAL
 VENTILATION.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 2405.2 SBC 1997. SEE PLANS FOR
 COMMENTS.
 4-SPECIFY THE DESIGN PRESSURES
 CALCULATED AT ALL EXTERIOR OPENINGS.
 SECTION 1606 SBC 1997.
 5-GARAGE SWING DOOR TO HAVE 32" MINIMUM
 CLEAR OPENING AS REQUIRED BY TABLE
 1004 SBC 1997. REVISE SIZE AS REQUIRED
 6-PROVIDE ATTIC ACCESS AS REQUIRED BY
 SEC 2309.6 SBC 1997.
 7-SPECIFY FASTENING OF ROOF SHEATHING.
 SEC. 2306 CITY AMENDMENTS TO SBC 1997.
 8-SPECIFY CONSTRUCTION AT GABLE END.
 PROVIDE WALL/SECTION SHOWING RAKE BM
 OR KNEE WALL AND COMPLETE FASTENERS.
 9-PROVIDE SOIL TEST REPORT.
 10-PROVIDE PRODUCT APPROVAL FOR:
 -SINGLE HUNG WINDOWS (DWGS NOT LEGIBLE)
 -OUTSWING DOOR (MISSING SOME DRAWINGS)
 11-STORM SHUTTERS: PROVIDE KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE (SEE
 CITY SAMPLE).