| Notes |
| Date |
Text |
| 2001-11-13 00:00:00 | ******************PROVISO*************** | | | | | | | | | MECHANICAL PERMIT 01071243 | | | | | | 1.DUCT SMOKE DETECTORS ARE REQUIRED | | | IF MORE THAN ONE AIR HANDLING UNIT | | | ARE TO BE RUN AT ANY GIVEN TIME. | | | (CFM WOULD BE GREATER THAN 2000 CFM) | | | | | | | | | 2.DUCT SMOKE DETECTORS SHALL BE TIED | | | BUILD BUILDING ALARM SYSTEMS AS PER | | | NFPA 90A 4-4.4.2. | | | | | | NOTE, CONDENSERS MOUNTED ON WALL SHALL | | | BE ACCESSIBLE. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|