| Plan Review Notes For Permit 01071207 |
| Permit Number |
01071207 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-18 00:00:00 | 1) CONDUITS IN STAIR TOWER BEING SHOWN | | | AS BEING BOXED OUT WITH 2 HOUR RATED | | | DRY WALL ENCLOSURE. AGAIN, NOTHING IS | | | PERMITTED TO BE LOCATED WITHIN THE STAIR | | | TOWER EXCEPT FOR FIRE PROTECTION PIPING | | | AND ELECTRICAL EQUIPMENT USED FOR | | | EMERGENCY LIGHTING. PLEASE REFER TO LIFE | | | SAFETY CODE, CHAPTER 5-1.3.2 | | | 2)NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. THE NEXTEL ROOM MUST BE FIRE | | | SPRINKLER PROTECTED EVEN WITH THE | | | INSTALLATION OF THE FM 200 SYSTEM. | | | PLEASE SUBMIT FIRE SPRINKLER DRAWINGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 832-2910 OR 659-8096 EXT. 8497 |
|