| Plan Review Notes For Permit 01071207 |
| Permit Number |
01071207 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | 1) THE NEW CONDUIT TO SAME PATH AS | | | EXISTING 3" PIPE SHOWN ON E-1 CANNOT | | | RUN THRU STAIRTOWER. NOTHING IS | | | PERMITTED TO ENTER THE STAIR EXCEPT | | | FIRE PROTECTION PIPING AND ELECTRICAL | | | EQUIPMENT USED FOR EMERGENCY LIGHTING. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF THE FM 200 | | | SYSTEM. THE FM 200 SYSTEM CANNOT | | | BE USED IN LIEU OF REQUIRED FIRE | | | SPRINKLER PROTECTION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|