2001-08-07 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT THE NEW SERVICE
 SHOWN IS NOT PERMITTED UNDER 230-2,
  
 2)NOTE: PLEASE NOTE GROUPING OF MAINS
 PER 230-72. PLEASE NOTE THAT A SHUNT
 TRIP AT EXSITING SERVICE LOCATION DOES
 NOT MEET 230-76 AND 230-79 FOR MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 PER 215-2 AND 230-42.
  
 PLEASE SUBMIT CLARIFICATION ON LOCATION
 OF SERVICES.
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  