| Plan Review Notes For Permit 01071207 |
| Permit Number |
01071207 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-07 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE NEW SERVICE | | | SHOWN IS NOT PERMITTED UNDER 230-2, | | | | | | 2)NOTE: PLEASE NOTE GROUPING OF MAINS | | | PER 230-72. PLEASE NOTE THAT A SHUNT | | | TRIP AT EXSITING SERVICE LOCATION DOES | | | NOT MEET 230-76 AND 230-79 FOR MEANS OF | | | DISCONNECT. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. | | | PER 215-2 AND 230-42. | | | | | | PLEASE SUBMIT CLARIFICATION ON LOCATION | | | OF SERVICES. | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|