Plan Review Notes
Plan Review Notes For Permit 01071206
Permit Number 01071206
Review Stop E
Sequence Number 3
Notes
Date Text
2001-10-18 00:00:00**************** UNSAT *************
  
 1)NOTE: PLANS STILL NEED TO BE
 SUBMITTEDFOR CHANGE OF USE, TO INCLUDE
 APPLICATION BY A CONTRACTOR SO THAT MAY
 CAN BE
 REVIEW FOR BLDG/PLUMB/HANDICAP CODE
 ISSUES.104.1.1
  
 2)NOTE: AS NOTED ON PREVIOUS REVIEWS
 COUNTY IMPACT FEES WILL NEED TO BE
 ADDRESSED.
  
 3)NOTE: PLEASE NOTE AND GIVE ALL INFOR-
 -MATION FOR FAIR HOUSING ACT REG,
 24 CFR 100.205
  
 4)NOTE: PLEASE NOTE ROOMS BEING ACCESS-
 -IBLE BY OTHER ROOMS AND YET PERMIT IS
 FOR MAKING NEW APTS???????
  
 5)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`S ON PLANS
 AND NEED TO CORRELATE WITH SUBMITTED
 PANEL
 SCHEDULES FOR NEW CIRCUITS AND
 SEPARATION BETWEEN UNITS???
  
 6)NOTE: PLEASE NOTE ONE KITCHEN SERVING
 MORETHAN ONE UNIT.????
  
 7)NOTE: MIN OF TWO SMALL APPLIANCE
 CIRCUITS PER 210-52.210-11-C-1
  
 8)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW HOW/WHERE A/C CIRCUITS ARE ???
 UNITS TO BE CALCULATED PER NAME PLATE
 RATINGS.
  
 9) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 10)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 11)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 FOR HOUSE LIGHTING.
  
 12)NOTE: PLEASE NOTE THAT NO GROUNDING
 IS SHOWN FOR ANYTHING. 250
  
 13)NOTE: PLEASE SUBMIT A ONE-LINE
 DIAGRAM SHOWING ALL PANELS/NEW AND OLD
 AND HOW THEY ARE FED? CONDUITS/FEEDERS
 ETC>
  
 14)NOTE: PLEASE NOTE THAT SOME BATHS
 DON'T SHOW ANY GFI OUTLETS. 210-52D
  
 15)NOTE: PLEASE NOTE THAT OCCUPANTS
 ARE REQ`D TO HAVE ACCESS TO PANELS
 FEEDING THEIR UNITS.
  
 16)NOTE:PLEASE NOTE PLANS NEED TO
 CLARIFY WASHING MACHINES AND OR DRYERS
 UNITS? GAS ? ELECTRIC??
  
 17)NOTE: PLEASE NOTE THAT LOAD EXCEEDS
 SERVICE ENTRANCE CONDUCTORS SIZE. PER
 310-16
  
 PERMIT APPLICATION NEEDS TO CLEARLY
 STATE WHAT IS BEING APPIED FOR AND
 OTHER REVIEW WILL NEED TO BE DONE.
 I SUGGEST ANOTHER MEETING BE SCHEDULED
 WITH ALL THAT MAY BE INVOLVED.
  
 PLEASE NOTE THAT THERE ARE PROBABLY
 MORE ELECTRICAL COMMENTS BUT PLANS
 ARE NOT COMPLETE ENOUGH TO MEET NEC
 REQUIREMENTS FOR COMMERCIAL APTS.
  
 PLEASE SUBMIT ALL OF THE ABOVE FOR
 REVIEW AND ADDRESS OTHER ISSUES.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
  
  
 ***** PLEASE NOTE****
 THAT COMPLETE VALUE OF TOTAL SCOPE OF
 WORK NEEDS TO BE SUBMITTED WITH PERMIT
 APPLICATION AND FEES AJUSTED.
 PER 104.7.5
 VALUE ON APPLICATION WAS CHANGED FROM
 ORIG SUBMITTAL AND FEES WERE NOT AJUSTED
 OWES FEES FOR RESUBMITTALS.