2001-07-25 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01071204
 326 ACACIA
  
 ARCH: SCHWAB, TWITTY & HANSER
 TEL: (561) 832-5599
 FAX: (561) 655-4828
 ENG: O'DONNELL, NACCMATO & MIGNOGNA
 TEL: (561) 835-9994
 FAX: (561) 835-8255
  
 1)- WILLIAM D. COOK P.E. NOT THE ENG.
 OF RECORD,NOT A WET SIGNATURE AND NOT A
 RAISED SEAL, WHAT PURPOSE DOES THIS ENG.
 INFORMATION HAVE WITH THIS DESIGN?
 2)- WILLIAM L. BROMLEY P.E. SIGNED
 & SEALED PLAN, HIS ENGINEER IS NOT THE
 ENGINEER OF RECORD, HE IS NOT THE ENG.
 CERTIFIYING THE TEST COMPLETED BY
 FENESTRATION TESTING LAB,WHY IS HIS SEAL
 ASSOCIATED WITH THIS DRAWING?
 3)- WHAT IS MISSING FOR ARCH ALUMINIUM
 GLASS & ALUMINIUM TESTING REPORT IS,
 THEY HAVEN'T APPLIED FOR PRODUCT APPROV-
 AL THROUGH ONE OF THE MODEL CODES.
 WE WILL ACCEPT SITE SPECIFIC FORM (A
 COPY-FOR FORMAT ONLY) IS ENCLOSED. THE
 ENGINEER WHO TESTED THE PRODUCT(FENES-
 TRATION TESTING,GILBERT DIAMOND P.E.)
 WOULD COMPLETE THE INFORMATION LISTED
 ON THE LEFT SIDE OF THE FORM, CERTIFY
 TO WHICH CODE THIS WAS TESTED,SOUTH FL.
 BUILDING CODE OR 1997 STANDARD BUILDING
 CODE, SSTD 12-97. THE RIGHT SIDE OF THE
 FORM(FORMAT) IS TO BE FILLED OUT BY THE
 ENGINEER OF RECORD (FOR THE BUILDING)
 CERTIFYING THAT SPECIFIC PRODUCT
 COMPLIES WITH THE PRESCRIBED PRESSURES
 THAT ARE FORMATED UNDER THE STANDARD
 BUILDING CODE, CERTIFYING THE GLAZED
 OPENINGS IN THIS BUILDING.
  
 BUILDING PLAN REVIEW