| Plan Review Notes For Permit 01071195 |
| Permit Number |
01071195 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PLAN SHEET A-1 ELECTRIC ROOM (241) | | | INDICATES A FIRE RATING OF 1 HOUR, | | | THERE IS NO FIRE DAMPER INICATED FOR | | | THE SUPPLY AIR TO THAT SPACE.THIS | | | ELECTRIC ROOM IS NOT IDENTIFIED ON | | | MECHANICAL PLAN TH-24, ROOM 241 ON | | | TH-24 IS THE STORAGE ROOM.ALSO, | | | SHOULD THE STORAGE ROOM HAVE A FIRE | | | RATING OF 1 HOUR AS THE ELEC. RM., | | | IT TOO WILL REQUIRE A FIRE DAMPER | | | ON THE SUPPLY AIR TO THAT SPACE. | | | | | | 2.WITH REGARD TO THE CARBON DIOXIDE | | | SENSOR IN THE CONFERENCE ROOM, AT | | | ANY GIVEN TIME OUTSIDE AIR REQUIRE- | | | MENTS SHALL NOT BE LESS THAN THAT | | | SPECIFIED IN ASHRAE 62-89. | | | | | | NOTE:FAN SHUTDOWN BY DUCT SMOKE | | | DETECTOR FOR UNITS LESS THAN | | | 2,000 CFM THAT SERVE AN AREA OF | | | EGRESS OR UNITS WITH AGGREGAGE | | | AIR TOTALING 2,000 CFM OR | | | GREATER. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|