2001-09-10 00:00:00*******************DENIED***************
  
  
 1.PLAN SHEET A-1 ELECTRIC ROOM (241)
 INDICATES A FIRE RATING OF 1 HOUR,
 THERE IS NO FIRE DAMPER INICATED FOR
 THE SUPPLY AIR TO THAT SPACE.THIS
 ELECTRIC ROOM IS NOT IDENTIFIED ON
 MECHANICAL PLAN TH-24, ROOM 241 ON
 TH-24 IS THE STORAGE ROOM.ALSO,
 SHOULD THE STORAGE ROOM HAVE A FIRE
 RATING OF 1 HOUR AS THE ELEC. RM.,
 IT TOO WILL REQUIRE A FIRE DAMPER
 ON THE SUPPLY AIR TO THAT SPACE.
  
 2.WITH REGARD TO THE CARBON DIOXIDE
 SENSOR IN THE CONFERENCE ROOM, AT
 ANY GIVEN TIME OUTSIDE AIR REQUIRE-
 MENTS SHALL NOT BE LESS THAN THAT
 SPECIFIED IN ASHRAE 62-89.
  
 NOTE:FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR FOR UNITS LESS THAN
 2,000 CFM THAT SERVE AN AREA OF
 EGRESS OR UNITS WITH AGGREGAGE
 AIR TOTALING 2,000 CFM OR
 GREATER.
  