2001-09-10 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT CLARIFICATION
 FOR GROUND OF TRANSFORMER PER 250-30
 CLARIFY POINT OF ATTACHMENT TO BLDG
 STEEL. AS IT IS NOT KNOWN IF THERE ARE\\
 ANY BREAKS IN COLD WATER LINE OF PVC.
  
 2)NOTE: PLEASE NOTE THAT AIC RATING WERE
 SUBMITTED FOR ALL PANELS. BUT PLEASE
 NOTE THAT THE AVAILABLE FAULT CURRENT IS
 SHOWN FOR MAIN BUT PLEASE SHOW WHAT THE
 ACTUAL RATING OF EQUIPMENT NEEDS TO BE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372