| Plan Review Notes For Permit 01071195 |
| Permit Number |
01071195 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT CLARIFICATION | | | FOR GROUND OF TRANSFORMER PER 250-30 | | | CLARIFY POINT OF ATTACHMENT TO BLDG | | | STEEL. AS IT IS NOT KNOWN IF THERE ARE\\ | | | ANY BREAKS IN COLD WATER LINE OF PVC. | | | | | | 2)NOTE: PLEASE NOTE THAT AIC RATING WERE | | | SUBMITTED FOR ALL PANELS. BUT PLEASE | | | NOTE THAT THE AVAILABLE FAULT CURRENT IS | | | SHOWN FOR MAIN BUT PLEASE SHOW WHAT THE | | | ACTUAL RATING OF EQUIPMENT NEEDS TO BE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|