| Plan Review Notes For Permit 01071195 |
| Permit Number |
01071195 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-14 00:00:00 | **************DENIED******************* | | | | | | PROVIDE OUTSIDE AIR SCHEDULE PER ASHRAE | | | 62-89. | | | | | | PROVIDE AIR BALANCE SHOWING COMPLIANCE | | | WITH SMC 501.2 | | | | | | VENTILATION REQUIRED FOR ELECTRIC ROOM | | | | | | OUTSIDE AIR REQUIRED FOR EQUIPMENT ROOM | | | (269) | | | | | | PROVIDE INFORMATION ON (EXISTING?) | | | RETURN AIR FROM THE SPACE TO THE A/C | | | UNIT. | | | | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR TO | | | BE TESTED. |
|