2001-08-14 00:00:00**************DENIED*******************
  
 PROVIDE OUTSIDE AIR SCHEDULE PER ASHRAE
 62-89.
  
 PROVIDE AIR BALANCE SHOWING COMPLIANCE
 WITH SMC 501.2
  
 VENTILATION REQUIRED FOR ELECTRIC ROOM
  
 OUTSIDE AIR REQUIRED FOR EQUIPMENT ROOM
 (269)
  
 PROVIDE INFORMATION ON (EXISTING?)
 RETURN AIR FROM THE SPACE TO THE A/C
 UNIT.
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR TO
 BE TESTED.